From symmetrical components, it is possible to derive the impedance Z at the IED
point for normal lines without mutual coupling according to equation
ph
ph
0
1
ph
N
ph
0
1
0
V
V
Z
Z
I
3
K
I
3I
3 Z
I
Z
=
=
-
+
×
+
×
×
EQUATION1275 V3 EN-US
(Equation 35)
Where:
Vph
is phase-to-ground voltage at the IED point
Iph
is phase current in the faulty phase
3I0
is ground-fault current
Z1
is positive sequence impedance
Z0
is zero sequence impedance
Z0m
A
B
21
21
en05000221_ansi.vsd
FAULT
ANSI05000221 V1 EN-US
Figure 72:
Class 1, parallel line in service
The equivalent circuit of the lines can be simplified, as shown in figure
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
197
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...