The normal mode
BuTripMode
=
1 out of 3
should have been verified in the tests above.
In applicable cases the modes
1 out of 4
and
2 out of 4
can be checked. Choose the mode
below, which corresponds to the actual case.
Checking the case
BuTripMode = 1 out of 4
It is assumed that the ground-fault current setting
Pickup_N
is below phase current setting
Pickup_PH
.
1.
Set
BuTripMode
=
1 out of 4
.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), with one-phase
current below set
Pickup_PH
but above
Pickup_N
. The residual ground-fault
should then be above set
Pickup_N
.
3.
Verify that back-up trip is achieved after set time. If selected, re-trip should also
appear.
4.
Disconnect AC and BFI_3P input signals.
Checking the case
BuTripMode = 2 out of 4
The ground-fault current setting
Pickup_N
may be equal to or below phase-current setting
Pickup_PH
.
1.
Set
BuTripMode
=
2 out of 4
.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), with one-phase
current above set
Pickup_PH
and residual (ground fault) above set
Pickup_N
.
3.
Verify that back-up trip is achieved after set time. If selected, re-trip should also
appear.
4.
Apply the fault condition, including initiation of CCRBRF (50BF), with at least one-
phase current below set
Pickup_PH
and residual (ground fault) above set
Pickup_N
.
The current may be arranged by feeding three- (or two-) phase currents with equal
phase angle (I0-component) below
Pickup_PH
, but of such value that the residual
(ground fault) current (3I
0
) will be above set value
Pickup_N
.
5.
Verify that back-up trip is not achieved.
6.
Disconnect AC and BFI_3P input signals.
11.5.8.6
Verifying instantaneous back-up trip at CB faulty condition
Applies in a case where a signal from CB supervision function regarding CB being faulty
and unable to trip is connected to input 52FAIL.
Section 11
1MRK 504 165-UUS -
Testing functionality by secondary injection
194
Transformer protection RET670 2.2 ANSI
Commissioning manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Страница 2: ......
Страница 18: ...12...
Страница 34: ...28...
Страница 66: ...60...
Страница 76: ...70...
Страница 94: ...88...
Страница 110: ...104...
Страница 292: ...286...
Страница 302: ...296...
Страница 308: ...302...
Страница 326: ...320...
Страница 327: ...321...