0.2
£
f(Ucos)
£
8Hz
AND
AND
PICKUP
Z cross line ZA - ZC
Z cross line ZC - ZB
AND
AND
ZONE1
ZONE2
Counter
N1Limit
a
b a
³
b
AND
TRIP1
Counter
N2Limit
a
b a
³
b
AND
TRIP2
OR
TRIP
ANSI07000100_2_en.vsd
Imin > 0.10
IBase
Vmax < 0.92
VBase
d
³
PickupAngle
d
£
TripAngle
ANSI07000100 V2 EN
Figure 39:
Logic diagram of the pole slip protection PSPPPAM (78)
11.4.11.2
Completing the test
Continue to test another function or end the test by changing the
TESTMODE
setting to
Disabled
. Restore connections and settings to their original values, if they were changed
for testing purposes.
11.4.12
Out-of-step protection OOSPPAM
The out-of-step protection (OOSPPAM (78)) function in the IED can be used for both
generator protection and as well for line protection applications.
The main purpose of the OOSPPAM (78) function is to detect, evaluate, and take the
required action during pole slipping occurrences in the power system.
The OOSPPAM (78) function detects pole slip conditions and trips the generator as fast
as possible, after the first pole-slip if the center of oscillation is found to be in zone 1,
which normally includes the generator and its step-up power transformer. If the center of
oscillation is found to be further out in the power system, in zone 2, more than one pole-
Section 11
1MRK 504 165-UUS -
Testing functionality by secondary injection
150
Transformer protection RET670 2.2 ANSI
Commissioning manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Страница 2: ......
Страница 18: ...12...
Страница 34: ...28...
Страница 66: ...60...
Страница 76: ...70...
Страница 94: ...88...
Страница 110: ...104...
Страница 292: ...286...
Страница 302: ...296...
Страница 308: ...302...
Страница 326: ...320...
Страница 327: ...321...