Test point
Reach
Set value
Comments
9
X
–0.4 x RLdFw x tan(ArgDir=20°)
R
0.4 x RLdFw
10
X
0.5 x X1
set
Exact –0.5 x R1
set
x tan(ArgNegRes=30°)
R
–0.23 x X1
set
11
X
0.8 x X1
set
Exact –0.5 x R1
set
x tan(ArgNegRes=30°)
R
–0.37 x X1
set
12
X
0.5 x X1
set
R
0.5 x R1
set
13
X
0
Only used when RLdFw > 0.5 x RFPP
R
0.5 x RFPP
is used in conjunction with figure
50%
80%
1
2
3
4
5
6
7
8
9
10
11
80% of RLdFwd
40% of RLdFwd
RFPG
12
ANSI05000369-2-en.vsd
13
a
alt. 80% of
RFPG (Load
encroachment)
120°
20°
ANSI05000369 V2 EN
Figure 24:
Distance protection characteristic with test points for phase-to-ground
measurements
is used in conjunction with figure
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
115
Commissioning manual