Table 31:
Test points for phase-to-ground C-G (Ohm/Loop)
Test point
Reach
Value
Comments
1
X
(2 x X1
set
+X0
set
)/3
R
0
2
X
(2 x X1
set
+ X0
set
)/3
R
2 x R1
set
+ R0
set
)/3
3
X
0.8 x (2 x X1
set
+ X0
set
)/3
R
0.8 x (2 x R1
set
+ R0
set
)/3
+RFPGZx
set
4
X
0.5 x (2 x X1
set
+ R0
set
)/3
R
0.5 x (2 x R1
set
+R0
set
)/3 +
RFPGZx
set
5
X
0.85 x RFPGZx
set
x tan(LdAngle
set
) LdAngle = angle for the maximal load
transfer
R
0.85 x RFPGZx
6
X
RLdFwdset x tan(LdAngleSet)
R
RLdFwd
set
7
X
0
R
RLdFwd
set
8
X
–02143 x RLdFwd
set
Exact: 0.8 x RFPGZx x tan (ArgDir=20°)
R
0.8 x RLdFwd
set
9
X
–0.8 x RLdFwd
set
x tan(ArgDir=20°)
R
0.8 x RLdFwd
set
10
X
0.17 x (2 x X1
set
+ X0
set
)
Exact: 0.5 x (2 x X1
set
X0
set
)/3
R
-0.36 x (2 x X1
set
+ X0
set
)
Exact: 0.5 x (2X1
set
+ X0
set
)/(3 x
tan(AgNegDir=30°)
11
X
0.27 x (2 x X1
set
+X0
set
)
Exact: 0.8 x (2 x X1
set
+ X0
set
)/3
R
–0.57 x (2 x X1
set
+ X0
set
)
Exact: 0.8 x (2X1
set
+ X0
set
)/(3 x
tan(AgNegDir=30°)
12
X
0.5 x (2 x X1
set
+ X0
set
)/3
R
0.5 x (2 x R1
set
+ R0
set
)/3
13
X
0
R
11.4.8.1
Measuring the operating limit of set values
Procedure:
Section 11
1MRK 504 165-UUS -
Testing functionality by secondary injection
140
Transformer protection RET670 2.2 ANSI
Commissioning manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Страница 2: ......
Страница 18: ...12...
Страница 34: ...28...
Страница 66: ...60...
Страница 76: ...70...
Страница 94: ...88...
Страница 110: ...104...
Страница 292: ...286...
Страница 302: ...296...
Страница 308: ...302...
Страница 326: ...320...
Страница 327: ...321...