<66>
Start /pick-up L
3
⃞
<67>
Start /pick-up N
⊠
<68>
General trip
⃞
<69>
Trip L
1
⃞
<70>
Trip L
2
⃞
<71>
Trip L
3
⃞
<72>
Trip I>> (back-up operation)
⃞
<73>
Fault location X in ohms
⃞
<74>
Fault forward/line
⃞
<75>
Fault reverse/busbar
⃞
<76>
Teleprotection signal transmitted
⃞
<77>
Teleprotection signal received
⃞
<78>
Zone 1
⃞
<79>
Zone 2
⃞
<80>
Zone 3
⃞
<81>
Zone 4
⃞
<82>
Zone 5
⃞
<83>
Zone 6
⃞
<84>
General start/pick-up
⊠
<85>
Breaker failure
⃞
<86>
Trip measuring system L
1
⃞
<87>
Trip measuring system L
2
⃞
<88>
Trip measuring system L
3
⃞
<89>
Trip measuring system E
⃞
<90>
Trip I>
⃞
<91>
Trip I>>
⃞
<92>
Trip IN>
⃞
<93>
Trip IN>>
Note: Function-specific fault signals are as default mapped to private data locations in 615 series IEDs.
3.3.3.6
Auto-reclosure indications in monitor direction
INF
Semantics
⊠
<128>
CB ’on’ by AR
⃞
<129>
CB ’on’ by long-time AR
⊠
<130>
AR blocked
Note <129>: Terms 'short-' or 'long-time' AR are not directly usable in 615 series. The AR
functionality in the IED performs AR shots (1..5) that are user configurable. See private AR data
definitions. Depending on user AR configuration it is possible to re-map some private data into
standard data, if wanted.
Section 3
1MRS756882 B
Interoperability profile for 615 series IEC 60870-5-103
24
REM615
Point List Manual