![ABB Relion REM615 Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/abb/relion-rem615/relion-rem615_manual_3407362021.webp)
IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
InUse
ASDU
GI
Coding
LD0.XAGGIO130.Ind4.stVal
-
XA130-Input 4
10=ON, 01=OFF
54
4
0
1
1
1
Generic operation time supervision
LD0.MDSOPT1.OpTmWrn.stVal
MDSOPT1.WARNING
Accum. operation time Warning
10=Warning
71
1
1
1
1
1
LD0.MDSOPT1.OpTmAlm.stVal
MDSOPT1.ALARM
Accum. operation time Alarm
10=Alarm
71
2
1
1
1
1
Negative sequence overcurrent protection for motors (2 stages)
LD0.MNSPTOC1.Str.general
MNSPTOC1.START
Stage1 start
10=Stage1 start
72
84
1
2
1
1
LD0.MNSPTOC1.Op.general
MNSPTOC1.OPERATE
Stage1 operate
10=Stage1 operate
72
90
1
2
0
1
LD0.MNSPTOC2.Str.general
MNSPTOC2.START
Stage2 start
10=Stage2 start
72
94
1
2
1
1
LD0.MNSPTOC2.Op.general
MNSPTOC2.OPERATE
Stage2 operate
10=Stage2 operate
72
91
1
2
0
1
Stalled motor protection
LD0.JAMPTOC1.Op.general
JAMPTOC1.OPERATE
Operate[.general]
10=Stage operate
73
90
1
2
0
1
Motor startup supervision
LD0.STTPMSS1.Str.general
STTPMSU.MOT_START
Motor startup in progress
10=Startup
74
84
1
2
1
1
LD0.STTPMSS1.Op.general
STTPMSU.OPR_IIT
Thermal stress operate
10=Operate
74
90
1
2
0
1
LD0.STTPRMI1.Op.general
STTPMSU.OPR_STALL
Stalling operate
10=Operate
74
91
1
2
0
1
Phase reversal protection
LD0.PREVPTOC1.Str.general
PREVPTEOC1.START
Stage start
10=Stage start
75
84
1
2
1
1
LD0.PREVPTOO1.Op.general
PREVPTEOC1.OPERATE
Stage operate
10=Stage operate
75
90
1
2
0
1
Motor thermal overload protection
LD0.MPPTR1.StrInh.general
MPTTR1.BLK_RESTART
Block restart
10=Block restart
76
83
1
2
1
1
LD0.MPPTR1.AlmThm.general
MPTTR1.ALARM
Thermal alarm
10=Alarm
76
85
1
2
1
1
LD0.MPPTR1.Op.general
MPTTR1.OPERATE
Thermal operate
10=Operate
76
90
1
2
0
1
Emegency start enabled
LD0.EMSGAPC1.Str.general
ESMGAPC1.ST_EMERG_E NA
Emergency start
10=Emergency start
77
84
1
2
1
1
Loss of load protection
LD0.LOFLPTUC1.Str.general
LOFLPTUC1.START
Stage1 start
10=Stage1 start
78
84
1
2
1
1
LD0.LOFLPTUC1.Op.general
LOFLPTUC1.OPERATE
Stage1 operate
10=Stage1 operate
78
90
1
2
0
1
ARC protection
LD0.ARCSARC11.FADet.stVal
ARCSARC1.ARC_FLT_DET
Stage1 Fault arc detected
10=Stage1 arc detected
156
211
1
1
0
1
LD0.ARCPTRC11.Op.general
ARCSARC1.OPERATE
Stage1 Operate
10=Stage1 operate
156
213
1
2
0
1
LD0.ARCSARC21.FADet.stVal
ARCSARC2.ARC_FLT_DET
Stage2 Fault arc detected
10=Stage2 arc detected
156
221
1
1
0
1
LD0.ARCPTRC21.Op.general
ARCSARC2.OPERATE
Stage2 Operate
10=Stage2 operate
156
223
1
2
0
1
LD0.ARCSARC31.FADet.stVal
ARCSARC3.ARC_FLT_DET
Stage3 Fault arc detected
10=Stage3 arc detected
156
231
1
1
0
1
LD0.ARCPTRC31.Op.general
ARCSARC3.OPERATE
Stage3 Operate
10=Stage3 operate
156
233
1
2
0
1
Non-directional earthfault protection, 2 stages (
ME01 only)
LD0.EFLPTOC1.Str.general
EFLPTOC1.START
Low(1) stage Start
10=Low(1) stage start
159
84
1
2
1
1
LD0.EFLPTOC1.Op.general
EFLPTOC1.OPERATE
Low(1) stage Operate
10=Low(1) stage operate
159
90
1
2
0
1
LD0.EFHPTOC1.Str.general
EFHPTOC1.START
High stage start
10=High Stage start
159
96
1
2
1
1
LD0.EFHPTOC1.Op.general
EFHPTOC1.OPERATE
High stage operate
10=High Stage operate
159
98
1
2
0
1
Table continues on next page
1MRS756882 B
Section 2
IEC 60870-5-103 data mappings
REM615
15
Point List Manual
Содержание Relion REM615
Страница 1: ...Relion 615 series Motor Protection and Control REM615 IEC 60870 5 103 Point List Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 35: ...29 ...