IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
InUse
ASDU
GI
Coding
LD0.SRGAPC1.Rs2.ctlVal
-
Reset SRGAPC1 flip-flop 2
10=Reset
11
102
1
20
0
1
LD0.SRGAPC1.Rs3.ctlVal
-
Reset SRGAPC1 flip-flop 3
10=Reset
11
103
1
20
0
1
LD0.SRGAPC1.Rs4.ctlVal
-
Reset SRGAPC1 flip-flop 4
10=Reset
11
104
1
20
0
1
LD0.SRGAPC1.Rs5.ctlVal
-
Reset SRGAPC1 flip-flop 5
10=Reset
11
105
1
20
0
1
LD0.SRGAPC1.Rs6.ctlVal
-
Reset SRGAPC1 flip-flop 6
10=Reset
11
106
1
20
0
1
LD0.SRGAPC1.Rs7.ctlVal
-
Reset SRGAPC1 flip-flop 7
10=Reset
11
107
1
20
0
1
LD0.SRGAPC1.Rs8.ctlVal
-
Reset SRGAPC1 flip-flop 8
10=Reset
11
108
1
20
0
1
Fuse failure protection
LD0.SEQRFUF1.Str.general
SEQRFUF1.FUSEF_U
General start
10=General start
22
84
1
2
1
1
LD0.SEQRFUF1.Str3Ph.general
SEQRFUF1.FUSEF_3PH
3 phase start
10=3 phase start
22
94
1
2
1
1
Current circuit failure protection
CTRL.CCRDIF1.Alm.stVal
CCRDIF1.FAIL
Current circuit failure alarm
10 = Alarm
23
1
1
1
1
1
CTRL.CCRDIF1.Op.general
CCRDIF1.ALARM
Current circuit failure operate
10 = Operate
23
90
1
2
0
1
Frequency protection, 2 stages (ME02,ME03
)
LD0.FRPTRC1.Str.general
FRPFRQ1.START
Stage 1 start
10 = Stage1 start
27
11
1
2
1
1
LD0.FRPTOF1.Op.general
FRPFRQ1.OPR_OFRQ
Operate 1 signal for overfrequency
10 = Stage1 overfrequency operate
27
12
1
2
0
1
LD0.FRPTUF1.Op.general
FRPFRQ1.OPR_UFRQ
Operate 1 signal for underfrequency
10 = Stage1 underfrequency operate
27
13
1
2
0
1
LD0.FRPFRC1.Op.general
FRPFRQ1.OPR_FRG
Operate 1 signal for frequency gradient
10= Stage1 frequency gradient operate
27
14
1
2
0
1
LD0.FRPTRC2.Str.general
FRPFRQ2.START
Stage 2 start
10 = Stage2 start
27
21
1
2
1
1
LD0.FRPTOF2.Op.general
FRPFRQ2.OPR_OFRQ
Operate 2 signal for overfrequency
10 = Stage2 overfrequency operate
27
22
1
2
0
1
LD0.FRPTUF2.Op.general
FRPFRQ2.OPR_UFRQ
Operate 2 signal for underfrequency
10 = Stage2 underfrequency operate
27
23
1
2
0
1
LD0.FRPFRC2.Op.general
FRPFRQ2.OPR_FRG
Operate 2 signal for frequency gradient
10 = Stage2 frequency gradient operate
27
24
1
2
0
1
Multipurpose analog protection functions (3 stages) (
ME01,ME02)
LD0.MAPGAPC1.Str.general
MAPGAPC1.START
Stage 1 Start
10 = Stage1 start
27
151
1
1
1
1
LD0.MAPGAPC1.Op.general
MAPGAPC1.OPERATE
Stage 1 Operate
10 = Stage1 operate
27
152
1
1
0
1
LD0.MAPGAPC2.Str.general
MAPGAPC2.START
Stage 2 Start
10 = Stage2 start
27
153
1
1
1
1
LD0.MAPGAPC2.Op.general
MAPGAPC2.OPERATE
Stage 2 Operate
10 = Stage2 operate
27
154
1
1
0
1
LD0.MAPGAPC3.Str.general
MAPGAPC3.START
Stage 3 Start
10 = Stage3 start
27
155
1
1
1
1
LD0.MAPGAPC3.Op.general
MAPGAPC3.OPERATE
Stage 3 Operate
10 = Stage3 operate
27
156
1
1
0
1
XRGGIO130 Alarm/Warning (ME01,ME02)
LD0.XRGGIO130.Wrn.stVal
XRGGIO130.WARNING
XRGGIO130 Warning
10 = Warning
27
201
0
1
0
1
LD0.XRGGIO130.Alm.stVal
XRGGIO130.ALARM
XRGGIO130 Alarm
10 = Alarm
27
202
0
1
0
1
Phase undervoltage protection (1 stage)
LD0.PHPTUV1.Str.phsA
-
Start[.phsA]
10=PhsA start
41
64
0
2
1
1
LD0.PHPTUV1.Str.phsB
-
Start[.phsB]
10=PhsB start
41
65
0
2
1
1
LD0.PHPTUV1.Str.phsC
-
Start[.phsC]
10=PhsB start
41
66
0
2
1
1
LD0.PHPTUV1.Str.general
PHPTUV1.START
Start[.general]
10=Start general
41
84
1
2
1
1
Table continues on next page
1MRS756882 B
Section 2
IEC 60870-5-103 data mappings
REM615
13
Point List Manual
Содержание Relion REM615
Страница 1: ...Relion 615 series Motor Protection and Control REM615 IEC 60870 5 103 Point List Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 34: ...28 ...
Страница 35: ...29 ...