IEC 61850 name
AFL-Common SA name
Description
DPI value
FUN
INF
InUse
ASDU
GI
Coding
CTRL.CCBRBRF1.OpEx.general
CCBRBRF1.TRBU
CBFP Failure, external trip
10=Failure,external trip
240
102
0
2
0
1
CTRL.CCBRBRF1.OpIn.general
CCBRBRF1.TRRET
CBFP Operate, internal retrip
10=Operate, internal re-trip
240
103
0
2
0
1
CTRL.CBCSWI1.Pos.stVal
CBXCBR1.POSITION
Circuit breaker position
10=Close; 01=Open; 00=Intermediate; 11=Error
240
160
1
1,20
1
2
Circuit breaker condition monitoring
LD0.SSCBR1.RsAccAPwr.ctlVal
SSCBR1.RST_IPOW
Reset accumulation energy
10=Reset
242
19
1
20
0
1
LD0.SSCBR1.RsCBWear.ctlVal
SSCBR1.RST_CB_WEAR
Reset CB remaining life and op.counters
10=Reset
242
20
1
20
0
1
LD0.SSCBR1.RsTrvTm.ctlVal
SSCBR1.RST_TRV_T
Reset CB travelling time alarm
10=Reset
242
21
1
20
0
1
LD0.SSCBR1.RsSprChaTm.ctlVal
SSCBR1.RST_SPR_T
Reset
CB
spring
charge
time
alarm
10=Reset
242
22
1
20
0
1
LD0.SSCBR1.OpnAlm.stVal
SSCBR1.TRV_T_OP_ALM
Open travel time exceeded
10=Open travel time alarm
242
101
0
1
0
1
LD0.SSCBR1.ClsAlm.stVal
SSCBR1.TRV_T_CL_ALM
Close travel time exceeded
10=Close travel time alarm
242
102
0
1
0
1
LD0.SSCBR1.SprChaAlm.stVal
SSCBR1.SPR_CHR_ALM
Spring charging time exceeded
10=Spring charging time alarm
242
103
0
1
0
1
LD0.SSCBR1.OpNumAlm.stVal
SSCBR1.OPR_ALM
Num of CB operations alarm
10=CB operations alarm
242
104
0
1
0
1
LD0.SSCBR1.OpNumLO.stVal
SSCBR1.OPR_LO
Num of CB operations lockout limit
10=CB operations lockout alarm
242
105
0
1
0
1
LD0.SSCBR1.LonTmAlm.stVal
SSCBR1.MON_ALM
CB 'not operated for long time' alarm
10=CB unactive alarm
242
106
0
1
0
1
LD0.SSCBR1.PresAlm.stVal
SSCBR1.PRES_ALM
Pressure below alarm level
10=Low pressure alarm
242
107
0
1
0
1
LD0.SSCBR1.PresLO.stVal
SSCBR1.PRES_LO
Pressure below lockout level
10=Low pressure lockout alarm
242
108
0
1
0
1
LD0.SSCBR1.APwrAlm.stVal
SSCBR1.IPOW_ALM
Acc.
currents
power
(Iyt),alarm
limit
10=Iyt alarm
242
109
0
1
0
1
LD0.SSCBR1.APwrLO.stVal
SSCBR1.IPOW_LO
Acc. currents power (Iyt),lockout limit
10=Iyt lockout alarm
242
110
0
1
0
1
LD0.SSCBR1.CBLifAlm.stVal
SSCBR1.CB_LIFE_ALM
Remaining life of CB exceeded alarm
10=CB life alarm
242
111
0
1
0
1
Disconnector positions
CTRL.DCSXSWI1.Pos.stVal
DCSXSWI1.POSITION
Disconnector 1 position
10=Close; 01=Open; 00=Intermediate; 11=Error
253
1
1
1
1
2
CTRL.DCSXSWI2.Pos.stVal
DCSXSWI2.POSITION
Disconnector 2 position
10=Close; 01=Open; 00=Intermediate; 11=Error
253
2
1
1
1
2
CTRL.DCSXSWI3.Pos.stVal
DCSXSWI3.POSITION
Disconnector 3 position
10=Close; 01=Open; 00=Intermediate; 11=Error
253
3
1
1
1
2
CTRL.ESSXSWI1.Pos.stVal
ESSXSWI1.POSITION
Earth switch position
10=Close; 01=Open; 00=Intermediate; 11=Error
253
11
1
1
1
2
LHMI alarm LED indications
LD0.LEDGGIO1.SPCSO1.stVal
-
LED 1 state
10=LED ON, 01=LED OFF
253
89
1
1
1
1
LD0.LEDGGIO1.SPCSO2.stVal
-
LED 2 state
10=LED ON, 01=LED OFF
253
90
1
1
1
1
LD0.LEDGGIO1.SPCSO3.stVal
-
LED 3 state
10=LED ON, 01=LED OFF
253
91
1
1
1
1
LD0.LEDGGIO1.SPCSO4.stVal
-
LED 4 state
10=LED ON, 01=LED OFF
253
92
1
1
1
1
LD0.LEDGGIO1.SPCSO5.stVal
-
LED 5 state
10=LED ON, 01=LED OFF
253
93
1
1
1
1
LD0.LEDGGIO1.SPCSO6.stVal
-
LED 6 state
10=LED ON, 01=LED OFF
253
94
1
1
1
1
LD0.LEDGGIO1.SPCSO7.stVal
-
LED 7 state
10=LED ON, 01=LED OFF
253
95
1
1
1
1
LD0.LEDGGIO1.SPCSO8.stVal
-
LED 8 state
10=LED ON, 01=LED OFF
253
96
1
1
1
1
Table continues on next page
1MRS756882 B
Section 2
IEC 60870-5-103 data mappings
REM615
17
Point List Manual