Direct transfer trip
Table 87. Low active power and power factor protection LAPPGAPC
Function
Range or value
Accuracy
Operate value, low active power
(2.0-100.0)% of SBase
±1.0% of S
r
Reset ratio, low active power
<105%
-
Operate value, low power factor
0.00-1.00
±0.02
Independent time delay to operate for low
active power at 1.2 x P
set
to 0.8 x P
set
(0.000-60.000) s
±0.2% or ±40 ms whichever is greater
Independent time delay to operate for low
power factor at 1.2 x PF
set
to 0.8 x PF
set
(0.000-60.000) s
±0.2% or ±40 ms whichever is greater
Critical impulse time, low active power
10 ms typically at 1.2 x P
set
to 0.8 x
P
set
-
Impulse margin time, low active power
10 ms typically
-
Table 88. Compensated over- and undervoltage protection COUVGAPC
Function
Range or value
Accuracy
Operate value, undervoltage
(1-100)% of UBase
±0,5% of U
r
Absolute hysteresis
(0.00–50.0)% of UBase
±0.5% of U
r
at U ≤ U
r
±0.5% of U at U > U
r
Critical impulse time, undervoltage
10 ms typically at 1.2 x U
set
to 0.8 x
U
set
-
Impulse margin time, undervoltage
15 ms typically
-
Operate value, overvoltage
(1-200)% of UBase
±0.5% of U
r
at U≤U
r
± 0.5% of U at U>U
r
Critical impulse time, overvoltage
10 ms typically at 0.8 x U
set
to 1.2 x
U
set
-
Impulse margin time, overvoltage
15 ms typically
-
Independent time delay for
undervoltage functionality at 1.2 x U
set
to 0.8 x U
set
(0.000-60.000) s
±0.2% or ±40 ms whichever is greater
Independent time delay for overvoltage
functionality at 0.8 x U
set
to 1.2 x U
set
(0.000-60.000) s
±0.2% or ±40 ms whichever is greater
Table 89. Sudden change in current variation SCCVPTOC
Function
Range or value
Accuracy
Operate value, overcurrent
(5-100)% of IBase
±2.0% of I
r
Hold time for operate signal at 0 to 2 x Iset
(0.000-60.000) s
±0.2% or ±15 ms whichever is
greater
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
ABB
97