Station communication
Table 156. Communication protocols
Function
Value
Protocol
IEC 61850-8-1
Communication speed for the IEDs
100BASE-FX
Protocol
IEC 60870–5–103
Communication speed for the IEDs
9600 or 19200 Bd
Protocol
DNP3.0
Communication speed for the IEDs
300–115200 Bd
Protocol
TCP/IP, Ethernet
Communication speed for the IEDs
100 Mbit/s
Protocol
LON
Communication speed for the IEDs
1.25 Mbit/s
Protocol
SPA
Communication speed for the IEDs
300–38400 Bd
Table 157. IEC 61850-9-2 communication protocol
Function
Value
Protocol
IEC 61850-9-2
Communication speed for the IEDs
100BASE-FX
Table 158. LON communication protocol
Function
Value
Protocol
LON
Communication speed
1.25 Mbit/s
Table 159. SPA communication protocol
Function
Value
Protocol
SPA
Communication speed
300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number
1 to 899
Table 160. IEC 60870-5-103 communication protocol
Function
Value
Protocol
IEC 60870-5-103
Communication speed
9600, 19200 Bd
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
112
ABB
Содержание RELION REL670
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 Product guide...
Страница 149: ...149...