2.5.2.6
CTRL.DCXSWI5 Disconnector control (5)
Table 126:
CTRL.DCXSWI5 Disconnector control (5)
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCXSWI5
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
2.5.2.7
CTRL.DCXSWI6 Disconnector control (6)
Table 127:
CTRL.DCXSWI6 Disconnector control (6)
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCXSWI6
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
2.5.2.8
CTRL.DCXSWI7 Disconnector control (7)
Table 128:
CTRL.DCXSWI7 Disconnector control (7)
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCXSWI7
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
2.5.2.9
CTRL.DCXSWI8 Disconnector control (8)
Table 129:
CTRL.DCXSWI8 Disconnector control (8)
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCXSWI8
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
2.5.2.10
CTRL.ESSXSWI1 Earthing switch indication (1)
Table 130:
CTRL.ESSXSWI1 Earthing switch indication (1)
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.ESSXSWI1
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
1MRS757807 B
Section 2
DNP3 data mappings
Remote Monitoring and Control REC615
53
Point List Manual