2.3
Binary inputs
Table 3:
Explanations of the binary input table columns
Column name
Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the input states.
2.3.1
System functions
2.3.1.1
CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
Table 4:
CTRL.LLN0 Local/remote state (also present in DNP IIN-bits)
IEC 61850 name
SA name
Description
Values
CTRL.LLN0
.Loc.stVal
Remote/Local state
0/1=Rem/Loc
2.3.1.2
LD0.GSEGGIO1 Goose supervision status (1)
Table 5:
LD0.GSEGGIO1 Goose supervision status (1)
IEC 61850 name
SA name
Description
Values
LD0.GSEGGIO1
.Alm.stVal
ALARM
Receiver alarm
1=Alarm
2.3.1.3
LD0.LLN0 Settings supervision
Table 6:
LD0.LLN0 Settings supervision
IEC 61850 name
SA name
Description
Values
LD0.LLN0
.SetChg.stVal
-
Settings changed
1=Changed
.SetSeld.stVal
-
Settings reserved
1=Reserved
Section 2
1MRS757807 B
DNP3 data mappings
18
Remote Monitoring and Control REC615
Point List Manual