Headline
Explanation
Invalid value set for PMU Parameters
There are two explanations possible:
Check if the following parameters are set
correctly on PMUREPORT:
ReportRate or
SvcClass or parameter PRIMVAL:
1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set
correctly on PMUREPORT:
ReportRate or
SvcClass or RptTimetag or parameter PRIMVAL:
1.FrequencySel is not set as 50Hz / 60Hz.
Invalid phase angle reference
The selected
PhaseAngleRef corresponds to an
analog channel that is not configured. Please
configure a valid reference channel.
GOOSE is configured on a disabled port
At least one of the access points configured for
GOOSE is disabled. The port can be disabled
either through changing the access point
operation to off or by unchecking the GOOSE
protocol from the access point in the Ethernet
configuration in PCM600 or LHMI.
Please enable GOOSE on access points:
AP_FRONT, AP_1
LDCM not running the application image
<slot number> is running the factory image
instead of the application image. The factory
image is older and does not contain the latest
updates and fixes.
Please reboot the IED. If the problem persists
update the LDCM firmware or replace the board.
LDCM version is not accepted
<device name> firmware version <version
string> is not accepted. The minimum accepted
version is <version string>.
Please update the LDCM firmware or replace the
board.
OEM not running the application image
OEM in slot <slot number> is running the factory
image instead of the application image. The
factory image is older and does not contain the
latest updates and fixes.
Please reboot the IED. If the problem persists,
update the OEM firmware or replace the board.
SFP unplugged from the slot
SFP has been unplugged from the slot
Please check the connection.
Corresponding hardware(s) is set to fail.
SFP replaced with other type
Configured and the detected SFP(s) are
different. Corresponding hardware(s) is set to
fail.
Please restart IED and consider Reconfigure HW
modules to get updated hardware list.
Non ABB vendor SFP detected
Non ABB vendor SFP detected.
Corresponding hardware(s) is set to fail. Please
use ABB approved SFP’s.
Section 13
1MRK 505 372-UEN A
Troubleshooting
176
Busbar protection REB670 2.2 IEC
Commissioning manual
Содержание RELION REB670
Страница 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 IEC Commissioning manual...
Страница 2: ......
Страница 14: ...8...
Страница 32: ...26...
Страница 46: ...40...
Страница 62: ...56...
Страница 66: ...60...
Страница 166: ...160...
Страница 176: ...170...
Страница 194: ...188...
Страница 195: ...189...