1MRK 505 353-UEN
Section 6
BP-Additions to base documentation
Application Manual
41
Bay protection functions REB500
Table 47
Definite time over and undercurrent protection 51 (PTOC/PTUC)
Function/ Parameter
Range/ Value
•
Pick-up current
0.2 to 20 I
N
in steps of 0.01 I
N
•
Delay
0.02 to 60 s in steps of 0.01 s
Reset ratio:
•
overcurrent
•
undercurrent
>94% (for max. function)
<106% (for min. function)
•
Max. operating time without delay
60 ms
•
Inrush restraint (optional):
•
pick-up setting
0.1 I
2h
/I
1h
·
Over- and undercurrent detection
·
Single or three-phase measurement with detection of the highest, respectively lowest phase current
·
2nd harmonic restraint for high inrush currents
·
4 independent parameter sets
Accuracies
Value
Accuracy of the pick-up setting (at f
N
)
±5%
Table 48
Inverse time overcurrent protection 51 (PTOC)
Function/ Parameter
Range/ Value
Inverse time characteristic
(acc. to B.S. 142, IEC 60255-3 with extended setting range):
•
normal inverse
•
very inverse
•
extremely inverse
•
long time inverse
t = k
1
/ ((I/I
B
)
C
- 1)
•
c = 0.02
•
c = 1
•
c = 2
•
c = 1
•
or RXIDG characteristic
t = 5.8 - 1.35 x·
l
n(I/I
B
)
•
Number of phases
1 or 3
•
Base current I
B
0.04 to 2.5 I
N
in steps of 0.01 I
N
Pick-up current I
start
1 to 4 I
B
in steps of 0.01 I
B
Min. time setting t
min
0 to 10 s in steps of 0.1 s
k
1
setting
0.01 to 200 s in steps of 0.01 s
·
Single or three-phase measurement with detection of the highest phase current
·
4 independent parameter sets