1MRK 505 353-UEN
Section 3
Configuring bay protection using HMI500
Application Manual
21
Bay protection functions REB500
the protection function is created when the mouse cursor changes to an arrow and
the mouse button is released.
Assigning protection functions to parameter sets
Every instance of a protection function can be assigned to a particular parameter
set. The REB500 runs the protection functions in the currently selected parameter
set. The active parameter set is changed by setting the appropriate binary input on
the bay unit.
Figure 5
Parameter set assignment
To assign the instance of a protection function to a parameter set, simply check the
corresponding box using the left mouse button.
Using the context menu
To open the context menu for a particular protection function, first select the func-
tion by clicking the left mouse button on its symbol and then clicking the right
mouse button.
Figure 6
Content menu
Table 38
Content menu dialogues
Menu item
Description
Copy
Creates a copy of the protection function according to the following rules:
• A copy cannot be in the same parameter set as the original.
• The input signals of a copy are the same as those of the original and
cannot be changed.
• Only defined parameters of a copy can be configured. All other param-
eters are taken from the original.