5.3.2.2
Mounting procedure for flush mounting
1
3
5
xx08000161.vsd
4
2
6
IEC08000161 V1 EN
Figure 11:
Flush mounting details.
PosNo Description
Quantity Type
1
Sealing strip, used to obtain IP54 class. The sealing strip is factory
mounted between the case and front plate.
-
-
2
Fastener
4
-
3
Groove
-
-
4
Screw, self tapping
4
2.9x9.5 mm
5
Joining point of sealing strip
-
-
6
Panel
-
-
Procedure
1.
Cut an opening in the panel (6).
1MRK 502 029-UEN A
Section 5
Installing the IED
33
Installation and commissioning manual