Check, that the output signals, issued for the first fault, correspond to a two-
trip for included phases. The output signals generated by the second fault
must correspond to the three-phase tripping action.
15.12.1.4
Circuit breaker lockout
The following tests should be carried out when the built-in lockout function is used
in addition to possible other tests, which depends on the complete configuration of
an IED.
1.
Check that
AutoLock
and
TripLockout
are both set to
Off
.
2.
Activate shortly the set lockout (SETLKOUT) signal in the IED.
3.
Check that the circuit breaker lockout (CLLKOUT) signal is set.
4.
Activate shortly thereafter, the reset lockout (RSTLKOUT) signal in the IED.
5.
Check that the circuit breaker lockout (CLLKOUT) signal is reset.
6.
Initiate a three-phase fault.
A three-phase trip should occur and all trip outputs TRL1, TRL2, TRL3
should be activated. Functional outputs TRIP and TR3P should be active at
each fault. The output CLLKOUT should not be set.
7.
Activate the automatic lockout function, set
AutoLock
=
On
and repeat
Beside the TRIP outputs, CLLKOUT should be set.
8.
Reset the lockout signal by shortly thereafter activating the reset lockout
(RSTLKOUT) signal.
9.
Activate the trip signal lockout function, set
TripLockout
=
On
and repeat.
All trip outputs (TRL1, TRL2, TRL3) and functional outputs TRIP and TR3P
must be active and stay active after each fault, CLLKOUT should be set.
10. Repeat.
All functional outputs should reset.
11. Deactivate the TRIP signal lockout function, set
TripLockout
=
Off
and the
automatic lockout function, set
AutoLock
=
Off
.
15.12.1.5
Completing the test
Continue to test another function or end the test by changing the
Test mode
setting
to
Off
. Restore connections and settings to their original values, if they were
changed for testing purposes.
15.13
Monitoring
15.13.1
Event function EVENT
Prepare the IED for verification of settings as outlined in section
and
section
in this chapter.
During testing, the IED can be set when in test mode from PST. The functionality
of the event reporting during test mode is set in the Parameter Setting tool in PCM600.
Section 15
1MRK 502 029-UEN A
Verifying settings by secondary injection
224
Installation and commissioning manual
Содержание Relion 670 series
Страница 1: ...Relion 670 series Generator protection REG670 Installation and commissioning manual...
Страница 2: ......
Страница 16: ...10...
Страница 24: ...18...
Страница 26: ...20...
Страница 28: ...22...
Страница 92: ...86...
Страница 96: ...90...
Страница 102: ...96...
Страница 108: ...102...
Страница 112: ...106...
Страница 126: ...120...
Страница 140: ...134...
Страница 150: ...144...
Страница 234: ...228...
Страница 238: ...232...
Страница 250: ...244...
Страница 259: ...253...