HMI Signal Name:
Status
Description
BOMn
READY / FAIL
BOM error. Binary output module Error
status.
IOMn
READY / FAIL
IOM-error. Input/Output Module Error
status.
MIMn
READY / FAIL
mA input module MIM1 failed. Signal
activation will reset the IED
RTC
READY / FAIL
This signal will be active when there is a
hardware error with the real time clock.
Time Sync
READY / FAIL
This signal will be active when the
source of the time synchronization is
lost, or when the time system has to
make a time reset.
Application
READY / FAIL
This signal will be active if one or more
of the application threads are not in the
state that Runtime Engine expects. The
states can be CREATED, INITIALIZED,
RUNNING, etc.
RTE
READY / FAIL
This signal will be active if the Runtime
Engine failed to do some actions with the
application threads. The actions can be
loading of settings or parameters for
components, changing of setting groups,
loading or unloading of application
threads.
IEC61850
READY / FAIL
This signal will be active if the IEC61850
stack did not succeed in some actions
like reading IEC61850 configuration,
startup etc.
LMD
READY / FAIL
LON network interface, MIP/DPS, is in
an unrecoverable error state.
LDCMxxx
READY / FAIL
Line Differential Communication Error
status
OEM
READY / FAIL
Optical Ethernet Module error status.
Also the internal signals, such as INT--FAIL and INT--WARNING can be
connected to binary output contacts for signalling to a control room.
In the IED Status - Information, the present information from the self-supervision
function can be viewed. Indications of failure or warnings for each hardware
module are provided, as well as information about the external time
synchronization and the internal clock. All according to table
. Loss of time
synchronization can be considered as a warning only. The IED has full
functionality without time synchronization.
18.1.2
Using front-connected PC or SMS
Here, two summary signals appear, self-supervision summary and numerical
module status summary. These signals can be compared to the internal signals as:
Section 18
1MRK 502 029-UEN A
Fault tracing and repair
240
Installation and commissioning manual
Содержание Relion 670 series
Страница 1: ...Relion 670 series Generator protection REG670 Installation and commissioning manual...
Страница 2: ......
Страница 16: ...10...
Страница 24: ...18...
Страница 26: ...20...
Страница 28: ...22...
Страница 92: ...86...
Страница 96: ...90...
Страница 102: ...96...
Страница 108: ...102...
Страница 112: ...106...
Страница 126: ...120...
Страница 140: ...134...
Страница 150: ...144...
Страница 234: ...228...
Страница 238: ...232...
Страница 250: ...244...
Страница 259: ...253...