corresponding function block in the application configuration, which protects or
controls the object that the symbol on the HMI page represents.
Creating a complete HMI display page
Procedure:
1. Make a sketch how to present the single line diagram.
2. Place the apparatus, transformer and other symbols that are needed for the
single line diagram into the raster boxes.
3. Add connection points where needed.
4. Link the apparatus symbols with line elements.
5. Adjust the text symbols while writing to north, east, south or west. Use the
object property window to do it.
6. Place measurements when needed.
7. Edit the name, unit and number of decimals of the measurements.
8. Select each object that has a dynamic link and do the link to the corresponding
9. Check to select the correct function block. Function blocks of the same type
can have different instance numbers.
10. Validate that all links are done.
11. Save the complete picture.
12. Repeat the steps for all pages when more than one is needed.
13. Write to IED.
IEC09000666-1-en.vsd
IEC09000666 V1 EN
Figure 49:
GDE: Establish a dynamic object link
Section 6
1MRK511240-UEN B
Local HMI engineering
66
670 series
Engineering Manual