For all practical engineering purposes (both towards the IED and towards the 61850
engineering process), the user should keep the default SCL technical key. It is however
possible, due to for example company naming policies, to rename the SCL technical
key for the station level, voltage level, bay level and IED level using the Object
properties window as shown in
.
•
The station level has been renamed as "DMSTAT"
•
The voltage level has been renamed as "C1"
•
The bay level has been renamed as "Q1"
•
The IED has been renamed as "SB1"
The renamed full path name of the technical key for the IED would be
DMSTATC1Q1SB1.
IEC08000374.vsd
IEC08000374 V1 EN
Figure 13:
PCM600: IEC 61850 signal designation concept
Section 4
1MRK 511 245-UUS -
Setting up a project
36
650 series ANSI
Engineering Manual