![ABB Relion 650 series ANSI Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/abb/relion-650-series-ansi/relion-650-series-ansi_engineering-manual_3483488030.webp)
IEC08000122.vsd
Make GOOSE connections
Export SCL files from
PCM600
Import SCL files to CCT600
and do signal engineering.
Export SCL files from
CCT600.
Import SCL files to PCM600
Write configuration
to IED
Start
HWT
ACT/
SMT
PST
GDE
SMT
CMT
Export
SCD
IED
WRITE
CCT600
Import
SCD
IED
WRITE
End
End
Optional, can be used to add
additional hardware modules
Configure IED functionality
Parametrization
Signal engineering
Create Single line diagram
for local HMI
Save the work
between the
different steps
Project
Create plant structure
Write configuration
to IED
IEC61850
Supported
protocols
IEC08000122 V1 EN
Figure 4:
IED engineering workflow
The described sequence in
is a proposal based on practical experience and
dependencies of the steps. It is possible to do a different sequence based on the
available information at the time the project is started. This means that several
iterations may be needed to finish the project.
•
Setting up the PCM600 project
Section 3
1MRK 511 245-UUS -
Engineering process
24
650 series ANSI
Engineering Manual