Attribute
DATA type
Explanation
M/O/E
Health
ABB_c_dINS
Health
M
NamPlt
ABB_a_dLPL
Name plate
M
Status
AnIN
ABB_a_dMV
Measurement Value
O
3.2.27
SPVNZBAT
Table 37:
SPVNZBAT
Attribute
DATA type
Explanation
M/O/E
ZBAT class
ZBAT
Station battery supervision
Data
Common logical node information
Mod
ABB_a_dINC
Mode
M
Beh
ABB_a_dINS
Behaviour
M
Health
ABB_c_dINS
Health
M
NamPlt
ABB_a_dLPL
Name plate
M
Status
Vol
ABB_b_dMV
Battery voltage
M
BatHi
ABB_a_dSPS
Battery high (voltage or charge -
overcharge)
O
BatLo
ABB_a_dSPS
Battery low (voltage or charge)
O
OpBatLo
ABB_v1_dSPS
Operate command when battery
voltage drops below lower limit
E
OpBatHi
ABB_v1_dSPS
Operate command when battery
voltage exceeds upper limit
E
Section 3
1MRS757261 E
Logical node extensions
30
PML630/Compact Load-Shedding Solution
Point List Manual