Table 70. Directional reactive power undervoltage protection (DQPTUV)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
Power:
1.5% or 0.002 × Q
n
(±1.5%) for power, PF -0.71...0.71
Voltage:
±1.5% of the set value or ±0.002 × U
n
Start time
1)
Typically 22 ms
Reset time
<40 ms
Reset ratio
Typically 0.96
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5 and so on
1)
Start value = 0.05 × S
n
, Reactive power before fault = 0.8 ×
Start value. Reactive power overshoot 2 times. Results based on statistical distribution of 1000 measurement.
Table 71. Directional reactive power undervoltage protection (DQPTUV) main settings
Parameter
Function
Value (Range)
Step
Voltage start value
DQPTUV
0.20...1.20 pu
0.01
Operate delay time
DQPTUV
0.1...300.00 s
0.01
Min reactive power
DQPTUV
0.01...0.50 pu
0.01
Min PS current
DQPTUV
0.02...0.20 pu
0.01
Pwr sector reduction
DQPTUV
0.0...10.0°
1.0
Table 72. Reverse power/directional overpower protection (DOPPDPR)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±3% of the set value or ±0.002 × S
n
Start time
1)2)
Typically 20 ms (±15 ms)
Reset time
<40 ms
Reset ratio
Typically 0.94
Retardation time
<45 ms
Operate time accuracy
±1.0% of the set value of ±20 ms
1)
U = U
n
, F
n
= 50 Hz, results based on statistical distribution of 1000 measurements.
2)
Includes the delay of the signal output contact.
Table 73. Reverse power/directional overpower protection (DOPPDPR) main settings
Parameter
Function
Value (Range)
Step
Directional mode
DOPPDPR
Forward
Reverse
-
Start value
DOPPDPR
0.01...2.00 pu
0.01
Power angle
DOPPDPR
-90.00...90.00°
0.01
Operate delay time
DOPPDPR
0.04...300.00 s
0.01
Generator Protection and Control
1MRS757583 C
REG630
Product version: 1.3
40