Table 55. High-impedance or flux-balance based differential protection for machines (MHZPDIF) main settings
Parameter
Function
Value (Range)
Step
Operate value
MHZPDIF
0.5...50.0%
0.1
Minimum operate time
MHZPDIF
0.02...300.00 s
0.01
Table 56. Stabilized differential protection for machines (MPDIF)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±3% of the set value or ±0.002 × I
n
Operate time
1)2)
Biased low stage
Instantaneous high
stage
3)
Typically 40 ms (±10 ms)
Typically 15 ms (±10 ms)
Reset time
<40 ms
Reset ratio
Typically 0.96
Retardation time
<20 ms
1)
Fn = 50 Hz, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the high speed power output contact
3)
Ifault = 2 ×
High operate value
Table 57. Stabilized differential protection for machines (MPDIF) main settings
Parameter
Function
Value (Range)
Step
CT connection type
MPDIF
1...2
1
High operate value
MPDIF
100...1000%
1
Low operate value
MPDIF
5...30%
1
Slope section 2
MPDIF
10.0...50.0%
0.1
End section 1
MPDIF
0...100%
1
End section 2
MPDIF
100...300%
1
Table 58. Three-phase overvoltage protection (PHPTOV)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
U
Fault
= 2.0 × set
Start value
Typically 17 ms (±15 ms)
Reset time
<40 ms
Reset ratio
Depends of the set
Relative hysteresis
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1)
Start value = 1.0 × U
n
, Voltage before fault = 0.9 × U
n
, f
n
= 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle
2)
Includes the delay of the signal output contact
3)
Maximum
Start value = 1.20 × U
n
,
Start value multiples in range of 1.10...2.00
Generator Protection and Control
1MRS757583 C
REG630
Product version: 1.3
36