Table 37. Non-directional earth-fault protection (EFxPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
EFLPTOC
0.010...5.000 pu
0.005
EFHPTOC
0.10...40.00 pu
0.01
EFIPTOC
0.10...40.00 pu
0.01
Time multiplier
EFLPTOC
0.05...15.00
0.01
EFHPTOC
0.05...15.00
0.01
Operate delay time
EFLPTOC
0.04...200.00 s
0.01
EFHPTOC
0.02...200.00 s
0.01
EFIPTOC
0.02...200.00 s
0.01
Operating curve type
1)
EFLPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
EFHPTOC
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
EFIPTOC
Definite time
1)
For further reference, see the Operation characteristics table
Table 38. Directional earth-fault protection (DEFxPDEF)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
DEFLPDEF
Current:
±1.5% of the set value or ±0.002 × I
n
Voltage
±1.5% of the set value or ±0.002 × U
n
Phase angle: ±2°
DEFHPDEF
Current:
±1.5% of the set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Voltage:
±1.5% of the set value or ±0.002 × U
n
Phase angle: ±2°
Start time
1)2)
DEFHPDEF and DEFLPTDEF:
I
Fault
= 2 × set
Start value
Typically 54 ms (±15 ms)
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1)
Set
Operate delay time = 0.06 s,Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × I
n
, f
n
= 50 Hz, earth-fault current with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum
Start value = 2.5 × I
n
,
Start value multiples in range of 1.5 to 20
Generator Protection and Control
1MRS757583 C
REG630
Product version: 1.3
30
ABB