Table 889:
29GS Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Event delay
0...60000
ms
1
30000
Event delay of the intermediate position
Vendor
0
External equipment vendor
Serial number
0
External equipment serial number
Model
0
External equipment model
9.2.8
Monitored data
Table 890:
52-TOC,29DS Monitored data
Name
Type
Values (Range)
Unit
Description
POSITION
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus position indication
Table 891:
29GS Monitored data
Name
Type
Values (Range)
Unit
Description
POSITION
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus position indication
9.2.9
Technical revision history
Table 892:
52-TOC, 29DS Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s and 30
s respectively for
Event delay settings.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced to
“FALSE” in case status is Faulty (11).
Table 893:
29GS Technical revision history
Technical revision
Change
B
Maximum and default values changed to 60 s and 30
s respectively for
Event delay settings.
C
Outputs
OPENPOS
and
CLOSEPOS
are forced to
“FALSE” in case status is Faulty (11).
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
975
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......