![ABB Relion 615 series Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_point-list-manual_3388490043.webp)
2.5.3.4
LD0.RESVMMXU1 Residual voltage (1)
Table 90:
LD0.RESVMMXU1 Residual voltage (1)
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
LD0.RESVMMXU1
.PhV.res.instCVal.mag
U0_INST
Residual voltage
0.00..4.00
[xUn]
R
0,4,0,400
2.5.3.5
LD0.HAEFMHAI1 Current harmonics
Table 91:
LD0.HAEFMHAI1 Current harmonics
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
LD0.HAEFMHAI
.HRmsA.res.cVal.mag
-
Current harmonics
0…250 [A]
R
0,250,0,250
2.5.4
Protection functions
2.5.4.1
LD0.T1PTTR1 Temperature protection values (1)
Table 92:
LD0.T1PTTR1 Temperature protection values (1)
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
LD0.T1PTTR1
.Tmp.mag
-
Object temperature
-100…9999.9
R
-100,9999.9.0,-1000,99999
.TmpRl.mag
-
Relative temperature
0…99.9
R
0,99.9,0,999
2.5.5
Protection-related functions
2.5.5.1
LD0.DARREC1 Autoreclosing values
Table 93:
LD0.DARREC1 Autoreclosing values
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
LD0.DARREC1
.AutoRecSt.stVal
STATUS
Autorec. status
-2…4
R
-2,4,-2,4
.ShotPntr.stVal
SHOT_PTR
Shot pointer value
0…65535
R
0,65535,0,65535
1MRS756879 D
Section 2
DNP3 data mappings
RED615
37