![ABB Relion 615 series Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_point-list-manual_3388490030.webp)
2.3.6
Protection-related functions
2.3.6.1
LD0.CCRDIF1 Current circuit failure protection
Table 48:
LD0.CCRDIF1 Current circuit failure protection
IEC 61850 name
SA name
Description
Values
LD0.CCRDIF1
.Alm.stVal
FAIL
Fail Alarm
1=Alarm
.Op.general
ALARM
Fail Operate
1=Operate
2.3.6.2
LD0.DARREC1 Autorecloser
Table 49:
LD0.DARREC1 Autorecloser
IEC 61850 name
SA name
Description
Values
LD0.DARREC1
.PrgRec1.stVal
INPRO_1
AR 1st reclose
1=In progress
.PrgRec2.stVal
INPRO_2
AR 2nd reclose
1=In progress
.PrgRec3.stVal
INPRO_3
AR 3rd reclose
1=In progress
.PrgRec4.stVal
INPRO_4
AR 4th reclose
1=In progress
.PrgRec5.stVal
INPRO_5
AR 5th reclose
1=In progress
.PrgRec.stVal
INPRO
AR in progress
1=In progress
.CBManCls.stVal
MAN_CB_CL
CB manually closed
1=CB closed
.LO.stVal
LOCKED
Lockout status
1=Lockout
.UnsRec.stVal
UNSUC_RECL
Reclose fail status
1=Failed
.InBlkThm.stVal
-
Thermal block (status)
1=Block
.RdyRec.stVal
READY
Ready reclose status
1=Ready
.ActRec.stVal
ACTIVE
Active reclose status
1=Active
.PrgDsr.stVal
DISCR_INPRO
Discrimination time in p.
1=In progress
.PrgCutOut.stVal
CUTOUT_INPRO
Cutout time in progress
1=In progress
.FrqOpAlm.stVal
FRQ_OP_ALM
Frequent operation alarm
1=Alarm
.RclTmStr.stVal
-
Reclaim time started
1=Started
.ProCrd.stVal
-
Protection coordination
1=In progress
.Op.general
CLOSE_CB
Operate (close XCBR)
1=Close CB
.OpOpn.general
OPEN_CB
Operate (open XCBR)
1=Open CB
.UnsCBCls.stVal
UNSUC_CB
CB closing failed
1=Failed
.WtMstr.stVal
CMD_WAIT
Master signal to follower
1=Signal
Section 2
1MRS756879 D
DNP3 data mappings
24
RED615
Point List Manual