2.3.4.2
LD0.RESCMMXU1 Residual current limit supervision
Table 15:
LD0.RESCMMXU1 Residual current limit supervision
IEC 61850 name
SA name
Description
Values
LD0.RESCMMXU1
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2.3.4.3
LD0.RESVMMXU1 Residual voltage limit supervision
Table 16:
LD0.RESVMMXU1 Residual voltage limit supervision
IEC 61850 name
SA name
Description
Values
LD0.RESVMMXU1
.HiAlm.stVal
HIGH_ALARM
High alarm
1=Alarm
.HiWrn.stVal
HIGH_WARN
High warning
1=Warning
2.3.5
Protection functions
2.3.5.1
LD0.LEDPTRC1 Global protection signals
Table 17:
LD0.LEDPTRC1 Global protection signals
IEC 61850 name
SA name
Description
Values
LD0.LEDPTRC1
Global protection signals
.Op.general
-
-General Operate
1=Operate
.Op.phsA
-
-phsA Operate
1=Operate
.Op.phsB
-
-phsB Operate
1=Operate
.Op.phsC
-
-phsC Operate
1=Operate
.Str.general
-
-General Start
1=Start
.Str.phsA
-
-phsA Start
1=Start
.Str.phsB
-
-phsB Start
1=Start
.Str.phsC
-
-phsC Start
1=Start
2.3.5.2
LD0.TRPPTRC1 Global conditioning (1)
Table 18:
LD0.TRPPTRC1 Global conditioning (1)
IEC 61850 name
SA name
Description
Values
LD0.TRPPTRC1
.Op.general
-
Operate input signal
1=Operate
.Tr.general
-
Trip output signal
1=Trip
1MRS756879 D
Section 2
DNP3 data mappings
RED615
17
Point List Manual