![ABB Relion 615 series Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_point-list-manual_3388490040.webp)
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
.ISCSO5.stVal
-
LED 5 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
.ISCSO6.stVal
-
LED 6 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
.ISCSO7.stVal
-
LED 7 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
.ISCSO8.stVal
-
LED 8 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
.ISCSO9.stVal
-
LED 9 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
.ISCSO10.stVal
-
LED 10 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
.ISCSO11.stVal
-
LED 11 state
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
2.5.2
Switchgear functions
2.5.2.1
CTRL.CBCSWI1 CB 4-pole (2 bit) position value
Table 78:
CTRL.CBCSWI1 CB 4-pole (2 bit) position value
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.CBCSWI1
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
2.5.2.2
CTRL.DCSXSWI1 Disconnector 1, 4-pole (2 bit) position values
Table 79:
CTRL.DCSXSWI1 Disconnector 1, 4-pole (2 bit) position values
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCSXSWI1
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
2.5.2.3
CTRL.DCSXSWI2 Disconnector 2, 4-pole (2 bit) position values
Table 80:
CTRL.DCSXSWI2 Disconnector 2, 4-pole (2 bit) position values
IEC 61850 name
SA name
Description
Values
S Arg 1,2,3,4
CTRL.DCSXSWI2
.Pos.stVal
POSITION
Intermediate=0; Off=1; On=2;
Bad=3
0…3
R
0,3,0,3
Section 2
1MRS756879 D
DNP3 data mappings
34
RED615