Table 12. IOM - Binary input/output module
Quantity
Rated value
Nominal range
Binary inputs
8
-
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL
±
20%
RL
±
20%
RL
±
20%
RL
±
20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency
10 pulses/s max
Oscillating signal discriminator
Blocking settable 1-40 Hz
Release settable 1-30 Hz
*Debounce filter
Settable 1-20 ms
Binary input operate time
(Debounce filter set to 0 ms)
3 ms
-
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
Line distance protection REL650
1MRK 506 384-BEN H
Version 2.2
Hitachi Power Grids
45
© 2017 - 2021 Hitachi Power Grids. All rights reserved