Table 55. Rate-of-change frequency protection SAPFRC , continued
Function
Range and value
Accuracy
Disengaging time *
fr = 50 Hz
Gs: ±0.05 Hz/s
Tested frequency slope:
1.2, 2.0, 5.0, 10.0 x Gs
Min. = 130 ms
Max. = 270 ms
Gs: ±5.00 Hz/s
Tested frequency slope:
1.2, 2.0 x Gs
Min. = 130 ms
Max. = 210 ms
Gs: ±10.00 Hz/s
Tested frequency slope:
1.2 x Gs
Min. = 130 ms
Max. = 160 ms
fr = 60 Hz
Gs: ±0.05 Hz/s
Tested frequency slope:
1.2, 2.0, 5.0, 10.0 x Gs
Min. = 100 ms
Max. = 210 ms
Gs: ±5.00 Hz/s
Tested frequency slope:
1.2, 2.0 x Gs
Min. = 100 ms
Max. = 170 ms
Gs: ±10.00 Hz/s
Tested frequency slope:
1.2 x Gs
Min. = 100 ms
Max. = 130 ms
Operate time delay *,
tDelay
Test conditions:
Gs: ± 0.2 Hz/s
Frequency slope: 0.4 Hz/s
Test points: 10%, 20%, 30%, 50%
and 100% of the time delay setting
range
fr = 50 Hz
(0.000-60.000) s
±0.2% or ±220 ms
whichever is greater
fr = 60 Hz
±0.2% or ±180 ms
whichever is greater
Reset time delay,
tReset
Test conditions:
Gs: ±0.2 Hz/s
Frequency slope: 0.4 Hz/s
fr = 50 Hz
(0.000-60.000) s
±0.2% or ±220 ms
whichever is greater
fr = 60 Hz
±0.2% or ±180 ms
whichever is greater
* The settings and test conditions are in accordance with IEC 60255-181 standard (section 6.2 – 6.7).
** The value ±0.05 Hz/s is used as minimum pickup value for frequency gradient.
Note! The stated accuracy is valid for phase-to-earth voltage range from 50 V to 250 V secondary. During testing three phase-to-earth voltages
with magnitude of 110/sqrt(3)=63.5 V were always used.
Line distance protection REL650
1MRK 506 384-BEN H
Version 2.2
76