The I Dir (I
0
cos(Angle)) function activates the START and STDIRIN output.
3.
Measure with angles
j
= /- 45° that the measuring element
operates when I
0
cos (
RCADir
-
j
) = I
0
cos(+/-45) =
INcosPhi>
.
4.
Compare the result with the set value.
Take the set characteristic into consideration, see figure
and figure
.
5.
Measure the operate time of the timer by injecting a current two times the set
INcosPhi>
value and the polarizing voltage 1.2 ·
UNRel>
.
( )
0
/ 3
cos
test
Tinv
kSN Sref
I
j
=
×
×
IECEQUATION2402 V1 EN
(Equation 1)
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Set the polarizing voltage to zero and increase until the boolean output signal
UNREL is activated, which is visible in the Application Configuration in
PCM600 when the IED is in online mode. Compare the voltage with the set
value
UNRel>
.
8.
Continue to test another function or complete the test by setting the test mode
to
Off
.
Operate area
ROADir
IEC06000650_2_en.vsd
=
o
0
RCADir
0
3
I
j
0
3
×
j
I cos
-
=
0
3
ref
U
U
IEC06000650 V2 EN
Figure 9:
Characteristic with ROADir restriction
1MRK 511 248-UEN -
Section 6
Testing functionality
45
Commissioning Manual