Section 6
Testing functionality
6.1
Testing disturbance report
6.1.1
Introduction
The following sub-functions are included in the disturbance report function:
•
Disturbance recorder
•
Event list
•
Event recorder
•
Trip value recorder
•
Indications
If the disturbance report is set on, then its sub-functions are also set up and so it is
not possible to only switch these sub-functions off. The disturbance report function
is switched off (parameter
Operation
=
Off
) in PCM600 or the local HMI under
Main menu/Settings/IED Settings/Monitoring/Disturbance report/
1:DRPRDRE
.
6.1.2
Disturbance report settings
When the IED is in test mode, the disturbance report can be made active or
inactive. If the disturbance recorder is turned on during test mode, recordings will
be made. When test mode is switched off all recordings made during the test
session are cleared.
Setting
OpModeTest
for the control of the disturbance recorder during test mode
are located on the local HMI under
Main menu/Settings/IED Settings/
Monitoring/Disturbance report/1:DRPRDRE
.
6.2
Identifying the function to test in the technical
reference manual
Use the technical manual to identify function blocks, logic diagrams, input and
output signals, setting parameters and technical data.
1MRK 511 248-UEN -
Section 6
Testing functionality
39
Commissioning Manual