Communication
58
Services Supported
Instance and Attributes
Two instances are supported by Class 0x91:
• Instance 1 for Output parameters.
• Instance 2 for Input parameters.
Instance 0x01, Attributes
Service Code
No.
Service Name
0x05
This Reset command will clear all attributes in
one instance to zero. I.e. a reset of Class 91,
Instance 1 will set all output parameters to zero.
0x0E
Get Attribute Single
0x10
Set Attribute Single
ID#
Attribute name
Default,
Min, Max
Data type
0x01 Output I/O parameter 1
0, 0, 32767 UINT16
0x02 Output I/O parameter 2
0, 0, 32767 UINT16
0x03 Output I/O parameter 3
0, 0, 32767 UINT16
0x04 Output I/O parameter 4
0, 0, 32767 UINT16
...
0x20 Output I/O parameter 32
0, 0, 32767 UINT16