4.
Fill the cable trenches and seal the cable entries. See chapter
.
Connecting the power grid cabling to the MV switchgear
See the MV switchgear manual and the wiring diagrams that are delivered with the compact
skid.
To connect the power grid cable to the MV switchgear:
1.
Remove the cable entry covers.
2.
Lead the cables into the compact skid and seal the cable entries.
3.
Terminate the cables according to the cable manufacturer instructions. Connect the
cables to the MV switchgear. The standard cable termination (see figure below) installed
in MV switchgear is of interface type C with bolted type 400 series.
Interface C with M16 x 2 metric threads
400 series, I
n
= 630 A
This termination is standard on all modules and for side connections.
4.
Fill the cable trenches and seal the cable entries. For more information, see chapter
Finalizing the installation (page 45)
.
5.
Connect the cables to correct terminals.
Note:
Maximum MV cable sizes depend on the connector dimensions. See MV switchgear
manual to determine the maximum cable size and configuration (see
and
).
44 Electrical installation