Technical data 53
Terminal and lead-through data for the control cables
I/O cables
Cable outer diameter:
• 5...7 mm 6 pcs
• 10...14 mm 2 pcs
Max. conductor size: 1.5 mm
2
/AWG 16
Tightening torques: 0.2 – 0.4 Nm
Aux. power cables
Cable outer diameter:
• 20...26 mm 2 pcs
• 10...14 mm 2 pcs
Tightening torques: *M12 70 Nm
AC output connection specification
Voltage
PVS800-57B-1645kW-C: 380 V AC 3-phase +/- 10%
PVS800-57B-1732kW-C: 400 V AC 3-phase +/- 10%
Allowed electrical system
type
3-phase IT (ungrounded) system. Galvanic isolation for each inverter is
needed.
Transformer
The transformer must be suitable for IGBT-based inverter use with high d
u
/d
t
values against the ground. Dedicated low-voltage winding is needed for each
inverter. Static screen between windings with proper dimensioning is
needed.
For details on selecting the transformer, refer to
page
Short-circuit withstand
strength (IEC 60439-1)
Maximum allowable prospective short-circuit current is 50 kA when protected
by fuses given in fuse tables.
When
temporary
grounding for work is applied (one set of grounding cables
are connected to the connecting knobs of the AC and DC busbars and PE of
the inverter): the maximum allowable prospective short-circuit current is
decreased to 40 kA / 1 s. If the connected grounding cables and clamps are
not equivalent to the prospective short-circuit rating of the inverter, the total
rating will be lower.
Frequency
45 to 65 Hz withstand with normal dimensioning (grid-compliance may
require disconnection at smaller values.) Maximum rate of change 17%/s
Imbalance
Max.
± 3% of nominal phase to phase AC line voltage
Voltage dips
Max. 0%
Fundamental power factor
(cos phi
1
)
1
Содержание PVS800-57B
Страница 1: ... ABB SOLAR INVERTERS PVS800 57B central inverters Hardware manual ...
Страница 4: ......
Страница 8: ...8 ...
Страница 16: ...16 Safety instructions ...
Страница 30: ...30 Operation principle and hardware description ...
Страница 32: ...32 Planning the mechanical installation ...
Страница 62: ...62 Dimension drawings Cabinet dimensions ...
Страница 63: ...Dimension drawings 63 ...
Страница 64: ...64 Dimension drawings Cabinet attachment points ...
Страница 65: ...Dimension drawings 65 ...
Страница 66: ...66 Dimension drawings AC and DC cabling lead throughs ...
Страница 67: ...Dimension drawings 67 ...
Страница 68: ...68 Dimension drawings AC cabling ...
Страница 69: ...Dimension drawings 69 ...
Страница 70: ...70 Dimension drawings DC cabling ...
Страница 71: ...Dimension drawings 71 ...
Страница 72: ...72 Dimension drawings ...