36 Planning the electrical installation
Selecting the power cables
General rules
Dimension the DC input power and AC output power cables
according to local
regulations
:
•
Dimension the cable to carry the inverter load current. See chapter
on
page
for the rated currents.
•
Select a cable rated for at least 90
°
C
(194
°
F)
maximum permissible temperature of
conductor in continuous use. Local regulations may require a higher temperature
rating.
•
The inductance and impedance of the PE conductor/cable (grounding wire) must be
rated according to permissible touch voltage appearing under fault conditions (so that
the fault point voltage will not rise excessively when a ground fault occurs).
•
Select an AC output cable rated for at least 0.6/1.0 kV AC and a DC input cable rated
for at least 1000 V DC.
A two-conductor system is allowed for the DC input cabling but a shielded cable can also
be used.
Symmetrical shielded cable is recommended for the AC output cabling; see section
Recommended AC output power cable types
below. Compared to a four-conductor
system, the use of symmetrical shielded cable reduces electromagnetic emission of the
whole inverter system.
Note:
When continuous metal conduit is employed, shielded cable is not required. The
conduit must have bonding at both ends as with cable shield.
To operate as a protective conductor, the shield conductivity requirements according to
IEC 61439-1 are shown below when the protective conductor is made of the same metal
as the phase conductors:
Cross-sectional area of
the phase conductors
Minimum cross-sectional
area of the corresponding
protective conductor
S (mm
2
) S
p
(mm
2
)
S < 16
S
16 < S < 35
16
35 < S
S/2
Shield
Содержание PVS800-57B
Страница 1: ... ABB SOLAR INVERTERS PVS800 57B central inverters Hardware manual ...
Страница 4: ......
Страница 8: ...8 ...
Страница 16: ...16 Safety instructions ...
Страница 30: ...30 Operation principle and hardware description ...
Страница 32: ...32 Planning the mechanical installation ...
Страница 62: ...62 Dimension drawings Cabinet dimensions ...
Страница 63: ...Dimension drawings 63 ...
Страница 64: ...64 Dimension drawings Cabinet attachment points ...
Страница 65: ...Dimension drawings 65 ...
Страница 66: ...66 Dimension drawings AC and DC cabling lead throughs ...
Страница 67: ...Dimension drawings 67 ...
Страница 68: ...68 Dimension drawings AC cabling ...
Страница 69: ...Dimension drawings 69 ...
Страница 70: ...70 Dimension drawings DC cabling ...
Страница 71: ...Dimension drawings 71 ...
Страница 72: ...72 Dimension drawings ...