40 Electrical installation
Routing the cables
When you route the cables:
•
Install the DC power, AC power and control cables on separate routes.
•
Make sure that the metallic cable trays are electrically bonded to each other and to the
ground.
•
Make sure that there is 500 mm (20 in) of separation between the power cables and
the control cables.
•
If the control cables cross the power cables, set them at angle as close to 90 degrees
as possible.
•
If you use four-conductor AC cabling, install the phase cables symmetrically and near
each other. Asymmetrical installation can induce current in the grounding cables and
metal structures.