76 Planning the electrical installation
Symmetrical shielded cable is recommended for the AC output cabling; see section
Recommended AC output power cable types
below. Compared to a four-conductor
system, the use of symmetrical shielded cable reduces electromagnetic emission of the
whole inverter system.
Note:
When continuous metal conduit is employed, shielded cable is not required. The
conduit must have bonding at both ends as with cable shield.
To operate as a protective conductor, the shield conductivity requirements according to
IEC 61439-1 are shown below when the protective conductor is made of the same metal
as the phase conductors:
To effectively suppress radiated and conducted radio-frequency emissions, the cable
shield conductivity must be at least 1/10 of the phase conductor conductivity. The
requirements are easily met with a copper or aluminum shield. The minimum requirement
of the cable shield is shown below. It consists of a concentric layer of copper wires with an
open helix of copper tape or copper wire. The better and tighter the shield, the lower the
emission level.
Cross-sectional area of
the phase conductors
Minimum cross-sectional
area of the corresponding
protective conductor
S (mm
2
) S
p
(mm
2
)
S < 16
S
16 < S < 35
16
35 < S
S/2
1
Insulation jacket
2
Copper wire screen
3
Helix of copper tape or copper wire
4
Inner insulation
5
Cable core
1
2
3
4
5
Содержание PVS800-57-0100kW-A
Страница 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Страница 4: ......
Страница 22: ...20 Safety instructions ...
Страница 64: ...62 Operation principle and hardware description ...
Страница 74: ...72 Mechanical installation ...
Страница 90: ...88 Electrical installation PE PE PE ...
Страница 124: ...122 Maintenance ...
Страница 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Страница 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Страница 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Страница 155: ...Dimension drawings 153 Frame R8i R8i 2 DC inputs option 2H382 or 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Страница 158: ...156 Dimension drawings R8i DC terminals of units with 2 DC inputs option 2H382 3AXD50000016935 ...
Страница 159: ...Dimension drawings 157 R8i DC terminals of units with 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 160: ...158 Dimension drawings R8i DC terminals of units with 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 162: ...160 Dimension drawings Frame 2 R8i 2 R8i 4 DC inputs option 4H382 or 5 DC inputs option 5H382 3AXD50000015007 ...
Страница 163: ...Dimension drawings 161 2 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015007 ...
Страница 164: ...162 Dimension drawings 2 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015007 ...
Страница 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Страница 170: ...168 Dimension drawings Frame 3 R8i 3 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015006 ...
Страница 171: ...Dimension drawings 169 3 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015006 ...
Страница 172: ...170 Dimension drawings 3 R8i 16 DC inputs option 16H382 or 20 DC inputs option 20H382 3AXD50000015006 ...
Страница 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Страница 178: ...176 Dimension drawings ...
Страница 179: ...Further information More information about ABB products for solar applications on the Internet www abb com solar ...
Страница 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...