74 Planning the electrical installation
Requirements for the transformer
•
suitable for the network and inverter AC voltage, current and power
•
suitable for use with IGBT inverters
•
degree of protection, temperature limits and lifetime are appropriate for the
environment
•
equipped with a static grounded screen between the high and low voltage windings
•
voltage withstand level of the low voltage winding is at least 1.6 kV against ground. A
typical voltage waveform against ground is shown below.
•
voltage rise time withstand level (d
u
/d
t
) of the low voltage winding is at least 1000 V
per microsecond against ground.
•
recommended rated short-circuit impedance (X
k
) for each inverter is approximately
6% (±1%)
•
withstands low-voltage side current DC components of at least 0.5% of the nominal
rated current preferably without using an air gap
•
withstands the 3% total harmonic distortion generated by the inverter. However, we
recommend dimensioning the transformer for at least 5% total harmonic distortion to
withstand possible outside interference from the network.
ABB recommends that the transformer is equipped with an off-load tap changer for voltage
regulation on the high-voltage side of the winding with two 2.5% step points to the plus and
minus directions.
The inverter does not require any specific transformer notation. ABB recommends using
traditional notations, such as Dy11d0, Dy11y11, etc.
Do not ground the neutral (star) point of the transformer or connect it to the neutral points
of other windings.
t
(ms)
U
AC-grid
(V)
Содержание PVS800-57-0100kW-A
Страница 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Страница 4: ......
Страница 22: ...20 Safety instructions ...
Страница 64: ...62 Operation principle and hardware description ...
Страница 74: ...72 Mechanical installation ...
Страница 90: ...88 Electrical installation PE PE PE ...
Страница 124: ...122 Maintenance ...
Страница 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Страница 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Страница 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Страница 155: ...Dimension drawings 153 Frame R8i R8i 2 DC inputs option 2H382 or 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Страница 158: ...156 Dimension drawings R8i DC terminals of units with 2 DC inputs option 2H382 3AXD50000016935 ...
Страница 159: ...Dimension drawings 157 R8i DC terminals of units with 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 160: ...158 Dimension drawings R8i DC terminals of units with 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 162: ...160 Dimension drawings Frame 2 R8i 2 R8i 4 DC inputs option 4H382 or 5 DC inputs option 5H382 3AXD50000015007 ...
Страница 163: ...Dimension drawings 161 2 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015007 ...
Страница 164: ...162 Dimension drawings 2 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015007 ...
Страница 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Страница 170: ...168 Dimension drawings Frame 3 R8i 3 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015006 ...
Страница 171: ...Dimension drawings 169 3 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015006 ...
Страница 172: ...170 Dimension drawings 3 R8i 16 DC inputs option 16H382 or 20 DC inputs option 20H382 3AXD50000015006 ...
Страница 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Страница 178: ...176 Dimension drawings ...
Страница 179: ...Further information More information about ABB products for solar applications on the Internet www abb com solar ...
Страница 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...