148 Technical data
Medium voltage network
The requirements of the EMC Directive can be met as follows:
1.
A transformer with static screening between the primary and secondary windings is used to ensure that
no excessive emission is propagated to neighboring low-voltage networks.
2.
The inverter is installed to an IT (ungrounded) system according to the instructions given in the hardware
manual.
Low-voltage network
The requirements of the EMC Directive can be met as follows:
1.
A transformer with static screening between the primary and secondary windings is used to ensure that
no excessive emission is propagated to neighboring low-voltage networks.
2.
The low-voltage network is of the TN type (grounded).
3.
The EMC filter (E216) is installed on network side of the low-voltage transformer.
4.
The inverter is installed according to the instructions given in the hardware manual.
“C-tick” marking
“C-tick” marking is required in Australia and New Zealand. A “C-tick” mark is attached to the inverter to verify
compliance with the relevant standards IEC/EN 61000-6-2:2005 and IEC/EN 61000-6-4:2007, mandated by
the Trans-Tasman Electromagnetic Compatibility Scheme.
For fulfilling the requirements of the standard, see section
Compliance with the European EMC directive
on
page
.
PVS800
Low-voltage
network
Equipment
Equipment
Medium voltage network
Static screen
Neighboring network
PVS800
Equipment
Low-voltage network
Static screen
EMC filter
1)
1)
E216
Содержание PVS800-57-0100kW-A
Страница 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Страница 4: ......
Страница 22: ...20 Safety instructions ...
Страница 64: ...62 Operation principle and hardware description ...
Страница 74: ...72 Mechanical installation ...
Страница 90: ...88 Electrical installation PE PE PE ...
Страница 124: ...122 Maintenance ...
Страница 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Страница 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Страница 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Страница 155: ...Dimension drawings 153 Frame R8i R8i 2 DC inputs option 2H382 or 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Страница 158: ...156 Dimension drawings R8i DC terminals of units with 2 DC inputs option 2H382 3AXD50000016935 ...
Страница 159: ...Dimension drawings 157 R8i DC terminals of units with 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 160: ...158 Dimension drawings R8i DC terminals of units with 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 162: ...160 Dimension drawings Frame 2 R8i 2 R8i 4 DC inputs option 4H382 or 5 DC inputs option 5H382 3AXD50000015007 ...
Страница 163: ...Dimension drawings 161 2 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015007 ...
Страница 164: ...162 Dimension drawings 2 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015007 ...
Страница 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Страница 170: ...168 Dimension drawings Frame 3 R8i 3 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015006 ...
Страница 171: ...Dimension drawings 169 3 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015006 ...
Страница 172: ...170 Dimension drawings 3 R8i 16 DC inputs option 16H382 or 20 DC inputs option 20H382 3AXD50000015006 ...
Страница 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Страница 178: ...176 Dimension drawings ...
Страница 179: ...Further information More information about ABB products for solar applications on the Internet www abb com solar ...
Страница 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...