![ABB PRO-33.0-TL Series Скачать руководство пользователя страница 80](http://html.mh-extra.com/html/abb/pro-33-0-tl-series/pro-33-0-tl-series_product-manual_4126080.webp)
80 Start-up
Remote monitoring setup
To set up the remote monitoring interface:
From
Menu
->
Communication
->
Embedded
Fieldbus
Set parameters:
To change parameter values:
1. Do the changes to a parameter.
2. Select the
Comm control
parameter.
3. Select
Refresh settings
.
Parameter
Values
Description
Protocol enable
Enables/disables the embedded
fieldbus interface and selects the
protocol to use.
None
No communication.
Modbus RTU
(default)
EFB is enabled and it uses the
Modbus RTU protocol.
Node address
1…247
(default: 1)
Node address of the inverter. All
devices must have different
addresses.
Baud rate
Sets the data transfer rate.
Autodetect
The inverter automatically sets the
transfer rate after monitoring traffic.
Note: Set the Parity parameter
before you enable autodetection.
9.6 kbps, 19.2 kbps,
38.4 kbps, 57.6 kbps,
76.8 kbps, 115.2 kbps
The default value is 19.2 kbps.
Parity
Sets the number of data bits, the
type of the parity bit and the number
of stop bits.
8 NONE 1
(default)
8 data bits, no parity bit, 1 stop bit
8 NONE 2
8 data bits, no parity bit, 2 stop bits
8 EVEN 1
8 data bits, even parity bit, 1 stop bit
8 ODD 1
8 data bits, odd parity bit, 1 stop bit
Содержание PRO-33.0-TL Series
Страница 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Hardware description ...
Страница 40: ...40 Installation requirements ...
Страница 70: ...70 Electrical installation ...
Страница 74: ...74 Installation checklist ...
Страница 110: ...110 Maintenance ...
Страница 134: ...134 Navigation map The navigation map ...
Страница 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...