114 Troubleshooting
28197 Backup/restore
timeout
Temporary communication
error between the control or
PC tool and the inverter.
Examine the communication, reset the fault
and do the operation again.
32267 FBA
communication
Communication between the
inverter and the fieldbus
adapter or between the master
controller and the fieldbus
adapter is lost.
1. Make sure that the master controller can
communicate.
2. Examine the adapter settings and status.
Refer to the user documentation of the
fieldbus interface.
3. Examine the cable connections.
32272 Ext. I/O
communication
loss
The inverter cannot
communicate with the
extension I/O module
1. Power down the inverter.
2. Make sure that the module is correctly
installed in Slot 1.
3. Restart the inverter.
If the same fault occurs again, the module
may be broken.
37120 Ground current
- Leakage current to ground
because of human, animal or
other contact between
electrical parts and ground.
- Leakage current to ground
because of water or high
humidity.
1. Power down the inverter.
2. Make sure that no people, animals or other
objects are in danger or in contact with the
electrical parts of the PV system.
3. Visually examine the cabling of the PV
system for faults or burn marks.
4. If the system looks normal, restart the
inverter.
If the same fault occurs again, immediately
isolate the inverter from all power sources.
Request a service visit from your system
supplier. Your PV system might have a
dangerous AC or DC side isolation fault and
contact to ground.
37121 RCMU sensor
Fault in the residual current
monitoring unit (RCMU).
1. Power down the inverter.
2. Restart the inverter.
If the same fault occurs again, immediately
isolate the inverter from all power sources
and contact your system supplier.
37122 Ground current
measurement
Fault in the internal ground
current measurement circuit.
1. Power down the inverter.
2. Restart the inverter.
If the same fault occurs again, power down
the inverter and contact your system supplier.
37123 Grid relay
Faulty grid relay.
1. Power down the inverter.
2. Restart the inverter.
If the same fault occurs again, power down
the inverter and contact your system supplier.
37130 HW mismatch
Internal HW board and SW
versions do not match.
1. Power down the inverter.
2. Restart the inverter.
If the same fault occurs again, power down
the inverter and contact your system supplier.
37136 String current
deviation
Note: Can also be
configured as a
warning.
Current deviation between
strings.
1. Read the aux code (1...8) from the Events
menu -> Active faults -> String current
deviations. The aux code number refers to the
affected string.
2. Examine the affected string for shading.
3. Make sure that the panels in the affected
strings do not have damage.
4. Make sure that the string monitoring
configuration settings are feasible.
Code Fault
Cause
What to do
Содержание PRO-33.0-TL Series
Страница 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Hardware description ...
Страница 40: ...40 Installation requirements ...
Страница 70: ...70 Electrical installation ...
Страница 74: ...74 Installation checklist ...
Страница 110: ...110 Maintenance ...
Страница 134: ...134 Navigation map The navigation map ...
Страница 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...