Technical data 129
Derating
The inverter monitors its internal temperature and derates the power output when
necessary to prevent damage to the inverter, protection devices and cabling. If the
temperature of the inverter rises or the operational currents are too high, the inverter
disconnects from the electrical grid and gives the overtemperature fault. When the
internal temperature decreases, the inverter connects to the grid again.
The nominal output power can be achieved in ambient temperatures of up to 45 °C
(113 °F) in the whole MPP operating voltage range. At the minimum MPP voltage
580 V
DC
, the nominal output power can be achieved even at 50 °C (122 °F). In the
ambient temperature range of 45…60 °C (113…140 °F), the output power is derated.
The power derating curves are applicable up to 1,000 m (3280 ft) above sea level. If
the inverter is installed above 1,000 m, the cooling capacity is reduced due to the
thinner air. The inverter temperature management attempts to compensate for the
reduced cooling. The power derating can start at temperatures lower than those
mentioned above.
Active power vs. temperature at power factor = 1:
580 Vdc
850 Vdc
950 Vdc
60
55
50
45
40
35
30
25
20
15
10
5
0
-5
-10
-15
-20
-25
35
30
25
20
15
10
5
0
P
max
(T) at PF=1
Ambient temperature (°C)
Maximum
Active Power (kW)
Содержание PRO-33.0-TL Series
Страница 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Hardware description ...
Страница 40: ...40 Installation requirements ...
Страница 70: ...70 Electrical installation ...
Страница 74: ...74 Installation checklist ...
Страница 110: ...110 Maintenance ...
Страница 134: ...134 Navigation map The navigation map ...
Страница 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...