Parameters 67
151.24
Protocol check
(
Visible only when parameter
is
FSCA-01.
)
Indicates whether parameters of the selected
communication protocol are loaded correctly. If
the value is not equal to the setting in parameter
, refresh settings with parameter
.
1
1
Parameters for Modbus RTU has been loaded
1
151.25
Protocol
(
Visible only when parameter
FSCA-01.
)
Selects the communication protocol for adapter
module.
Modbus
Modbus
Modbus RTU selected
1
N2
Not applicable
2
FLN
Not applicable
3
BACnet
Not applicable
4
DCP
Not applicable
5
151.26
Protocol sw ver
(
Visible only when parameter
FSCA-01.
)
Shows the software version of the selected
communication protocol.
-
151.27
FBA par refresh
Commits any changed adapter module
configuration parameter settings.
After refresh, the value reverts to 0 = Done.
Done
Done
Refreshing done.
0
Refresh/Configure
Refreshing.
1
151.28
Par table ver
Adapter parameter table version (internal use)
-
151.29
Drive type code
Adapter inverter type code (Internal use)
620
151.30
Mapping file ver
Mapping file version (Internal use)
-
151.31
D2FBA comm sta
Displays the communication status of the adapter
module.
Idle
Idle
Adapter is not configured.
0
Exec. Init
Adapter is initializing.
1
Time out
A timeout has occurred in the communication
between the adapter and the inverter.
2
Conf.err
Adapter configuration error: The major or minor
revision code of the common program revision in
the adapter module is not the revision required by
the module or mapping file upload has failed
more than three times.
3
Off-line
Adapter is off-line.
4
On-line
Adapter is on-line.
Note
: This is the normal operation state unless
the parameters timeout and the Timeout mode is
set to non-default values. See parameters
,
,
and
5
Reset
Adapter is performing a hardware reset.
6
151.32
FBA comm SW ver
Shows the common program revision of the
adapter module
-
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
Содержание PRO-33.0-TL Series
Страница 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Страница 4: ......
Страница 8: ...8 ...
Страница 12: ...12 Service menu ...
Страница 36: ...36 Program features ...
Страница 100: ...100 Parameters ...
Страница 112: ...112 Tools ...
Страница 121: ......
Страница 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...