Figure 10.3
.
Filtering to curve for harmonic order n
The programming procedure consists in:
1) Defining the Mode of operation.
2) Specifying the harmonics to be filtered and the permitted residual level
(=curve) for each of them. At 50 Hz, 20 harmonics between the 2
nd
and
50
th
may be selected. At 60 Hz, 15 harmonics between the 2
nd
and 50
th
.
3) Programming reactive power compensation parameters
10.6.2.
Keys identification.
Filtered current
Remaining
current
Before filtering
After filtering
Permitted
residual level
=
curve
Load current
for harmonic
order n
Numerical
keypad
Arrow
buttons
‘OK’
button
‘MENU’
button
Delete
button