PositionMaster EDP300
| CI/EDP300-EN Rev. C 13
6.3
Mechanical mounting
6.3.1
General information
Fig. 3:
Operating range
Arrow
1
on the device feedback shaft (position feedback
point) must move between the arrow marks
2
.
Fig. 4:
Measuring and operating ranges of the positioner
1
Measuring range
2
Operating range
Operating range for linear actuators:
The operating range for linear actuators is ±45° symmetrically
to the longitudinal axis. The usable span within the operating
range is at least 25° (recommended figure 40°). The usable
span does not necessarily need to run symmetrically to the
longitudinal axis.
Operating range of rotary actuators:
The usable span is 90°, which must be entirely within the
measuring range, but does not necessarily need to run
symmetrically to the longitudinal axis.
NOTICE
During installation make sure that the actuator travel or
rotation angle for position feedback is implemented correctly.
6.3.2
Mounting on linear actuators
For mounting on a linear actuator in accordance with DIN /
IEC 534 (lateral mounting as per NAMUR), the following
attachment kit is available:
Fig. 5:
Components of attachment kit
1
Screw
2
Washer
3
Attachment bracket
4
Level with
follower pin (for travel 10 … 35 mm (0.39 … 1.8 inch) or 20 … 100 mm
(0.79 … 3.94 inch)
5
Washers
6
Screws
7
U-Bolts
8
Washers
9
Nuts
j
Screws
k
Spring washers
l
Clamp
plates
m
Follower guide
M
10
4
0
8-
01
1
2
M11103
+45°
-45°
-135°
+135°
1
2
M
10
4
13
-
01
1
2
3
4
5
6
7
8
9
j
k
l
m
Содержание PositionMaster EDP300
Страница 1: ...Commissioning Instruction CI EDP300 EN Rev C PositionMaster EDP300 Digital Positioner...
Страница 34: ...34 CI EDP300 EN Rev C PositionMaster EDP300 12 2 Control Drawing 901305...
Страница 35: ...PositionMaster EDP300 CI EDP300 EN Rev C 35...
Страница 36: ...36 CI EDP300 EN Rev C PositionMaster EDP300...
Страница 37: ...PositionMaster EDP300 CI EDP300 EN Rev C 37...
Страница 38: ...38 CI EDP300 EN Rev C PositionMaster EDP300...
Страница 39: ...PositionMaster EDP300 CI EDP300 EN Rev C 39...