background image

41-973.5R

10

Type PM Line of Relays For Pilot Wire Monitoring

And Transferred Tripping

ping is used), to prevent the possibility of inad-
vertently tripping the associated circuit breaker
during testing. If the relays do not perform as
expected, and diode failure is suspected, the
diode tests described in the following section
may be performed.

8.3

RECTIFIER (DIODE) CHECK 

(AC RELAYS ONLY)

If there is suspicion of a rectifier (diode) failure, apply
30 volts dc reverse voltage (positive on cathode)
through a 300 ohm resistance to the diode. Measure
the voltage across the diode. If this voltage is not
essentially 30 volts, the diode is short circulated.
Now apply 30 volts dc in the forward direction
through the 300 ohm resistor, and measure the volt-
age across the resistor. If the voltage is not essen-
tially 30 volts, the diode may have a high forward
resistance. If voltage is zero, the diode is open-cir-
cuited.

9.0 CALIBRATION

If the relay has been dismantled or the calibration
has been disturbed, use the following procedure for
calibration. (Relays must be tested in the case.)

With the permanent magnet removed, see that the
moving armature floats in the central area of the air-
gap between the poles of the polar unit frame. If nec-
essary, loosen the core screw in the center rear of
the unit and shift the core and contact assembly until
the armature floats. (This can best be done with the
polar unit removed from the relay.) Then retighten the
core screw and replace he permanent magnet with
the dimple (north pole) on the magnet to the left
when viewed from the front.

9.1

POLAR UNITS – GENERAL

The following mechanical adjustments are given as a
guide, and some deviation from them may be neces-
sary to obtain proper electrical calibration.

9.1.1

Magnetic Shunt Adjustment

The sensitivity of the polar unit is adjusted by means
of two magnetic, screw-type shunts at the rear of the
unit, as shown in figure 1. These shunt screws are
held in proper adjustment by a flat strip spring across
the back of the polar unit frame, so no locking screws
are required. Looking at the relay, front view, turning
out the right-hand shunt to open the right-hand air
gap decreases the amount of current required to
close the right-hand contact. Conversely, drawing out
the left-hand shunt increases the amount of current
required to close the right-hand contact, or

decreases the amount of current required to close
the left-hand contact (with the proper direction of cur-
rent flow). Also, if a relay trips to the right at the
proper current, the dropout current can be raised by
turning in the right-hand shunt. The two shunt-screw
adjustments are not independent, however, and a
certain amount of trimming adjustment of both shunt
screws is generally necessary to obtain the desired
pickup and dropout calibration.

In general, the farther out the two shunt screws are
turned, the greater the toggle action will be, and as a
result, the lower the dropout current. For the tripping
units (3) of the PM-3, PM-13, and PM-23 relays, tog-
gle action is desirable, with a dropout current around
75 percent of the pickup current. For the monitoring
alarm relay units, toggle action is not desired.
Instead, the armature is adjusted to float between the
pole faces at a given current (1 or 2 mA), and to
move gradually toward the high or low current alarm
as the coil current is increased or decreased. Simi-
larly, the floating adjustment of the armature of the
ground alarm unit (5) requires that both shunt screws
be turned in relatively far. Then the armature will
move gradually to the left or right as the current
through the two #5 coils is unbalanced.

The electrical calibration of the polar unit is also
affected by the contact adjustment as this changes
the position of the polar unit armature. Do not change
the contact adjustment without rechecking the electri-
cal calibration. 

The chart on page 11 indicates the units present in
each relay.

9.1.2

Contact Adjustment – all relays

For all monitoring alarm units, designed (1) or (2),
turn in all the stationary contact and contact stop
screws until they just touch the moving contact.
Advance the screws to hold the armature in the cen-
tral portion of the magnetic air gap between the two-
pole faces. (The stationary contact screws have a
round silver contact face; the stop screws do not
have this silver facing.) Now back off all the contact
and contact stop screws one full turn. This will give a
total contact travel of 0.050 inch. When the relay is
properly calibrated, some touch-up adjustment may
be necessary so that double contacts will both close
at the same current value. The contact gap between
the floating moving contact and the right-hand or left-
hand stationary contacts or contact stops will be
approximately 0.025 inch when the relay is in opera-
tion.

For the tripping (3) units of the PM-3, PM-13, PMG-

Содержание PMA

Страница 1: ...M 13 PMG 13 or PM 23 relays are used Table 1 illustrates the functions available with each relay A 10 mfd Capacitor is supplied with each PM relay This capacitor provides an ac path between the two ha...

Страница 2: ...23 PM 2 1 Polar Alarm Unit 2 1 Polar Trip Unit 3 1 Indicating Contactor Switch ICS 1 Milliammeter 5 0 mA 1 Set of Adjustable and Fixed Resistors 2 Blocking Rectifiers 1 Polar Alarm Unit 2 1 Milliamme...

Страница 3: ...t pro vides restraint for the armature and thus controls the pickup value of the switch PMD MDG 13 with Tel Relay In the relays type PMD and PMG 13 where they are energized with dc power supply the gr...

Страница 4: ...PMG 13 source relays has its midpoint grounded through a current limiting resistor Thus a pilot wire ground will cause an increase in current in one coil circuit and a decrease in the other one This u...

Страница 5: ...tap block to the desired setting by means of a screw connection 4 9 TRIP CIRCUIT CONSTANT Indicating Contactor Switch ICS 5 0 SETTINGS Operating units of all relays are adjusted in the fac tory to th...

Страница 6: ...S FOR DC REMOTE TRIPPING 2 REQUIRED PER STATION Line Terminals dc Voltage Station A PMG 13 or PM 13 Station B PM 2 PM 3 or PM 23 or PM 4 Station C PM 2 PM 3 or PM 23 or PM 4 To Operate 2 3 48 125 250...

Страница 7: ...unting Theterminal studs maybe easily removed or inserted by locking two nuts on the stud andthen turning the proper nut with a wrench For detailed FT case information refer to Instruction Leaflet 41...

Страница 8: ...t wire ground test To check the pickup current of the ground detector first remove to the 20 000 ohm resistor from terminals 6 and 7 Connect a 0 1 dc milliammeter in series with a variable resis tor o...

Страница 9: ...istors can readily be seen from the external schematic figure 27 7 1 8 PMG 13 Relays ac and dc Alarm and Tripping Units Follow the procedure given in the previous section for the ac and dc PM 13 relay...

Страница 10: ...to close the right hand contact or decreases the amount of current required to close the left hand contact with the proper direction of cur rent flow Also if a relay trips to the right at the proper c...

Страница 11: ...etic shunts all the way in then back them out five turns each With the relay ener gized at rated voltage set the monitoring current at 1 3 or 2 3 mA dc for 2 or 3 terminal relay respectively by adjust...

Страница 12: ...t be blocked open so as not to affect the tripping unit pickup This will give approximately 2 mA through the relay coil Now draw out the left hand shunt until the relay resets with toggle action not g...

Страница 13: ...armature will move gradually as the current is changed for this relay unit 9 1 10 ICS Unit Close the main relay tripping contact circuit with a jumper connected directly across the contact termi nals...

Страница 14: ...c supply three terminal line page 23 20 PMG 13 Relay ac supply two or three terminal line page 24 21 PMG 13 Relay dc supply with Telephone Relay Output two terminal line page 24 22 PMG 13 Relay dc sup...

Страница 15: ...ferred Tripping Figure 2 Internal Schematic of the Type PMA Relay in FT 31 case 120 volt 60 hertz supply for two terminal lines Figure 3 Internal Schematic of Type PMA 1 Relay in the FT 21 case 120 vo...

Страница 16: ...ansferred Tripping Figure 4 Internal Schematic of Type PMA Relay in FT 31 case 120 volt 60 hertz supply for three terminal lines Figure 5 Internal Schematic of Type PMA 1 Relay in FT 21 case 120 volt...

Страница 17: ...ring And Transferred Tripping Figure 6 Internal Schematic of the Type PMD Relay in FT 21 case dc supply for two terminal lines Figure 7 Internal Schematic of the Type PMD 1 Relay in the FT 11 case dc...

Страница 18: ...And Transferred Tripping Figure 8 Internal Schematic of the Type PMD Relay in the FT 21 case dc supply for three terminal lines Figure 9 Internal Schematic of the Type PMD 1 Relay in the FT 11 case d...

Страница 19: ...f Relays For Pilot Wire Monitoring And Transferred Tripping Figure 10 Internal Schematic of the Type PM 2 Relay in the FT 21 case Figure 11 Internal Schematic of the Type PM 3 Relay in the FT 11 case...

Страница 20: ...2 Internal Schematic of the Type PM 4 Auxiliary Unit in the small molded case Figure 13 Internal Schematic of the Type PM 5 Ground Detector Relay in the FT 11 case Sub 7 2D1845 Sub 2 184A501 POS POS W...

Страница 21: ...Wire Monitoring And Transferred Tripping Figure 14 Internal Schematic of the Type PM 23 Relay in the FT 21 case Figure 15 Internal Schematic of the Type PM 13 Relay in the FT 32 case dc supply for tw...

Страница 22: ...red Tripping Figure 16 Internal Schematic of the type PM 13 Relay in the FT 32 case dc supply for three terminal lines Figure 17 Internal Schematic of the Type PM 13 Relay in the FT 32 case 120 volt 6...

Страница 23: ...nd Transferred Tripping Figure 18 Internal Schematic of the Type PMG 13 Relay in the FT 32 case dc supply for two terminal lines Figure 19 Internal Schematic of the type PMG 13 Relay in the FT 32 case...

Страница 24: ...ipping Figure 20 Internal Schematic of the Type PMG 13 Relay in the FT 32 case 120 volts 60 hertz supply for two or three terminal lines Figure 21 PMG 13 Relay with Ground Alarm and Remote Trip two te...

Страница 25: ...sferred Tripping Figure 22 PMG 13 Relay with Ground Alarm and Remote Trip three terminal lines with Telephone Relay output FT 32 case Figure 23 PMD Relay Ground Alarm D P D T Contacts two terminal lin...

Страница 26: ...3 5R 26 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 24 PMD Relay Ground Alarm D P D T Contacts three terminal lines with Telephone Relay Output FT 21 case Sub 3 34...

Страница 27: ...41 973 5R 27 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 25 External Schematic of the type PMD Relay with Type PM 23 or PM 4 Relay two terminal lines Sub 4 719B530...

Страница 28: ...41 973 5R 28 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 26 External Schematic of the Type PMA Relay with Type PM 23 or PM 4 Relay two terminal lines Sub 8 290B247...

Страница 29: ...973 5R 29 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 27 External Schematic of the dc Type PMG 13 Relay with Type PM 23 or PM 4 Relay two terminal lines Sub 5 719B...

Страница 30: ...973 5R 30 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 28 External Schematic of the Type PMD Relay with Type PM 23 and PM 4 Relays three terminal lines Sub 4 719B5...

Страница 31: ...41 973 5R 31 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 29 External Schematic of the ac Type PMG 13 with Type PM 23 Relay two terminal lines Sub 7 290B250...

Страница 32: ...5R 32 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 30 External Schematic of the dc Type PM 13 and PM 5 Relay with Type PM 23 or PM 4 Relay two terminal lines Sub 6...

Страница 33: ...973 5R 33 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 31 External Schematic of the dc Type PM 13 Relay with Type PM 23 or PM 4 Relay two terminal lines Sub 6 290B2...

Страница 34: ...For Pilot Wire Monitoring And Transferred Tripping Figure 32 Outline and Drilling Plan for 10 mfd capacitor for references only Figure 33 Outline and Drilling Plan for External Remote Trip Resistor A...

Страница 35: ...oring And Transferred Tripping Sub 1 184A989 Figure 34 Outline and Drilling Plan for the Type PM 4 auxiliary Unit in the projection molded case Figure 35 Outline and Drilling Plan for the Type PM 4 Au...

Страница 36: ...41 973 5R 36 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 36 Outline and Drilling Plan for the Type PM 3 PM 5 PMD 1 Relays in the Type FT 11 case 57D7900 Sub 20...

Страница 37: ...973 5R 37 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 37 Outline and Drilling Plan for the Type PM 2 PM 23 PMA 1 and PMD Relays in the Type FT 21 case Sub 17 57D79...

Страница 38: ...41 973 5R 38 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 38 Outline and Drilling Plan for the Type PMA Relay in the Type FT 31 case Sub 17 57D7902...

Страница 39: ...41 973 5R 39 Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping Figure 39 Outline and Drilling Plan for the Type PM 13 and PMG 13 Relays in the Type FT 32 case Sub 17 57D7903...

Страница 40: ...B Automation Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd Printed in U S A ABB Automation Inc 4300 Coral Ridge Drive...

Отзывы: